1592040000 XR30-60-70T EN v1.3 2020.08.26
XR30-60-70T
22/40
AUS
SAA
Set point for auxiliary regulator
5.0
Pr2
°C
[-100.0°C to 150.0°C]
[-148.0°F to 302.0°F]
AUS
SHy
Auxiliary regulator differential
2.0
Pr2
°C
[0.1°C to 25.0°C]
[0.1°F to 45.0°F]
AUS
ArP
Probe selection for auxiliary regulator
nP
Pr2
nP(0); P1(1); P2(2); P3(3); P4(4)
AUS
Sdd
Auxiliary regulator disabled during any
defrost cycle
no
Pr2
n(0); Y(1)
AUS
btA
Base time for parameters Ato and AtF
SEC
Pr2
SEC; Min
AUS
Ato
Interval of time with auxiliary output ON
0
Pr2
sec
0 to 255 sec/min
AUS
AtF
Interval of time with auxiliary output OFF
0
Pr2
sec
0 to 255 sec/min
ALr
ALP
Probe selection for temperature alarms
P1
Pr1
nP(0); P1(1); P2(2); P3(3); P4(4)
ALr
ALC
Temperature alarms configuration: relative,
absolute
Ab
Pr1
rE(0); Ab(1)
ALr
ALU
High temperature alarm
150.0
Pr1
°C
°C[0.0° to 50.0° or ALL to
150.0°]
°F[0.0° to 90.0° or ALL to 302.0°]
ALr
ALL
Low temperature alarm
-100.0
Pr1
°C
°C[0.0° to 50.0° or -100.0° to
ALU]
°F[0.0° to 90.0° or -148.0° to
ALU]
ALr
AFH
Temperature alarm differential
2.0
Pr1
°C
[0.1°C to 25.0°C]
[0.1°F to 45.0°F]
ALr
ALd
Temperature alarm delay
0
Pr1
min
0 to 255 min
ALr
dot
Temperature alarm delay with open door
00:00
Pr1
mm:ss
0.0 to 24min00sec
ALr
dAo
Temperature alarm delay at start-up
00:00
Pr1
hh:mm
0.0 to 24h00min
ALr
AP2
Probe selection for second temperature
alarm
P2
Pr2
nP(0); P1(1); P2(2); P3(3); P4(4)
ALr
AU1
Pre-alarm threshold for second
temperature alarm (absolute value)
150.0
Pr2
°C
[-100.0°C to 150.0°C]
[-148.0°F to 302.0°F]
ALr
AH1
Second high temperature pre-alarm
differential
2.0
Pr2
°C
[0.1°C to 25.0°C]
[0.1°F to 45.0°F]
ALr
Ad1
Second high temperature pre-alarm delay
255
Pr2
min
0 to 255 min
ALr
AL2
Second low temperature alarm
-100.0
Pr2
°C
[-100.0°C to 150.0°C]
[-148.0°F to 302.0°F]
ALr
AU2
Second high temperature alarm
150.0
Pr2
°C
[-100.0°C to 150.0°C]
[-148.0°F to 302.0°F]
ALr
AH2
Second temperature alarm differential
2.0
Pr2
°C
[0.1°C to 25.0°C]
[0.1°F to 45.0°F]
ALr
Ad2
Second temperature alarm delay
0
Pr2
min
0 to 255 min
ALr
dA2
Second temperature alarm delay at start-
up
00:00
Pr2
hh:mm
0.0 to 24h00min
ALr
bLL
Compressor OFF due to second low
temperature alarm
no
Pr2
n(0); Y(1)
ALr
AC2
Compressor OFF due to second high
temperature alarm
n
Pr2
n(0); Y(1); MAn(2)
ALr
SAF
Differential for anti-freezing control
-1.0
Pr2
°C
[-12.0°C to 12.0°C]
[-21.6°F to 21.6°F]
ALr
tbA
Alarm relay deactivation
no
Pr2
n(0); Y(1)
oUt
oA2
Relay output oA2 configuration
dEF
Pr2
nu(0); CP1(1); dEF(2); FAn(3);
ALr(4); LiG(5); AUS(6); db(7);
onF(8); HES(9); Cnd(10);
CP2(11); dF2(12); HEt(13);
inv(14)
oUt
oA3
Relay output oA3 configuration
FAn
Pr2
nu(0); CP1(1); dEF(2); FAn(3);
ALr(4); LiG(5); AUS(6); db(7);
onF(8); HES(9); Cnd(10);
CP2(11); dF2(12); HEt (13);
inv(14)