Section 8: Customizing Smart EHO Settings
Customizing Smart EHO Settings
MENU NAME
MENU
KEY
CONFIGURATION/
CALIBRATION VALUE
DEFAULT
ACTION
FREQUENCY CONFIGURATION
The power supply frequency configuration.
Note: This will be factory set.
Fc
0 = DC
1 = 50 Hz
2 = 60 Hz
3 = Not defined
Feedback
Only
PHASE CONFIGURATION
The power supply phase configuration.
Note: This will be factory set.
Pc
0 = Single Phase
1 = Three Phase
Feedback
Only
HYDRAULIC LEAK ALARM DEBOUNCE COUNT
Set the maximum number of Valve Drift Alarms
allowed per hour. If Valve Drift Alarm Frequency
is more than the Hydraulic leak Alarm Debounce
Count, then the Hydraulic Leak Alarm will be
generated. If Valve Drift Alarm is less than the
Hydraulic Leak Alarm Debounce Count then
Hydraulic Leak Alarm will be automatically cleared.
dC
2 to 10
2
LOW OIL ALARM ENABLE
If oil level sensor is present, then this parameter can
be used to Enable or Disable the Low Oil Alarm.
LO
0 = Disable
1 = Enable
Feedback
Only
DISCRETE INPUT SETUP
Set the discrete input logic.
di
Yes/No
N/A
DISCRETE INPUT 1
Set if Discrete Input for OPEN command should be
Active on Close contact or Open Contact.
d1
0 = Active on Close
contact
1 = Active on Open
contact
0 = Active
on Close
contact
DISCRETE INPUT 2
Set if Discrete Input for CLOSE command should
be Active on Close contact or Open Contact.
d2
0 = Active on Close
contact
1 = Active on Open
contact
0 = Active
on Close
contact
DISCRETE INPUT 3
Set if Discrete Input for STOP/PST command should
be Active on Close contact or Open Contact.
d3
0 = Active on Close
contact
1 = Active on Open
contact
0 = Active
on Close
contact
DISCRETE INPUT 4
Set if Discrete Input for OPEN INHIBIT command
or OIL LEVEL SENSOR input should be Active on
Close contact or Open Contact.
d4
0 = Active on Close
contact
1 = Active on Open
contact
0 = Active
on Close
contact
DISCRETE INPUT 5
Set if Discrete Input for CLOSE INHIBIT command
should be Active on Close contact or Open Contact.
d5
0 = Active on Close
contact
1 = Active on Open
contact
0 = Active
on Close
contact
DISCRETE OUTPUT SETUP
Set the configurable output relays customer can
use to monitor for various parameters. Refer to
wiring diagram for relay terminal connection.
dO
Yes/No
N/A