68
September 2020
Service Instructions
MAN-02-08-77-0714-EN Rev. 2
Section 8: Customizing Smart EHO Settings
Customizing Smart EHO Settings
Table 23.
Configuration Table (12)
MENU NAME
MENU
KEY
CONFIGURATION/
CALIBRATION VALUE
DEFAULT
ACTION
ANALOG CONFIGURATION
CA
Yes/No
n/a
ANALOG OUTPUT 1 SOURCE
Configure the Analog Out 1 Source to
provide feedback on various parameters from the
actuator to the host system.
A1
0 = Position
1 = Setpoint
2 = Host Control
3 = Hydraulic Circuit
Pressure
0 = Position
ANALOG OUT 2 SOURCE
Configure the Analog Out 2 Source to
provide feedback on various parameters from the
actuator to the host system.
A2
0 = Position
1 = Setpoint
2 = Host Control
3 = Hydraulic Circuit
Pressure
3 = Hydraulic
Circuit Pressure
ENABLE LOST ANALOG INPUT 1 ALARM
Enable an alarm if analog input signal is lost.
The actuator must be set up for analog input.
Ae
0 = Disable
1 = Enable
1 = Enable
LOST ANALOG ALARM DELAY
If Analog Signal is disconnected, then Lost Analog Alarm
would be generated after this delay.
Ad
0 to 60 Seconds
0 = 0 Seconds
LOST ANALOG INPUT ACTION
Configure the actuator to move to a configurable
position when analog input signal is lost. The actuator
must be set up for analog input and the configurable
position can be configured only through the DCMlink.
Ai
0 = stay put
1 = go to configurable
position
1 = go to
configurable
position
LOST ANALOG SIGNAL - SETPOINT
Configure the actuator to move to a
setpoint if the analog signal is lost.
AS
0-100
The values 0 and 100
would be displayed as
OPEN/CLOSE according to
Close Direction
30(%)
ANALOG INPUT POLARITY CLOSE
Configure the analog input signal polarity.
iP
0 = 4 - 20 mA (zero-span)
1 = 20 - 4 mA (zero-span)
0 = 4 - 20 mA
(zero-span)
ANALOG OUTPUT POLARITY CLOSE
Configure the analog output signal polarity.
Note: this will reverse the analog signals configured in
Analog Output 1[A1] and Analog Output 2[A2].
oP
0 = 4 - 20 mA (zero-span)
1 = 20 - 4 mA (zero-span)
0 = 4 - 20 mA
(zero-span)
ANALOG CALIBRATION
Calibrate Analog Input and Output channels.
Ac
Yes/No
N/A
ANALOG INPUT CALIBRATION
Calibrate the analog input channel with an external
current source. External current source needs to be
connected to source 4 mA equivalent signal when this
menu is being flashed. The signal has to be in the range
3.6 mA - 22 mA.
iC
Yes/No
N/A
CALIBRATE LOWER LIMIT OF ANALOG INPUT CHANNEL
Calibrate the 4 mA value for the analog input channel.
iL
Yes/No
N/A
LOWER LIMIT VALUE CALIBRATED
(CALIBRATION STATUS)
If the current value input through the Analog Input
channel is in valid range, then the device will be
calibrated successfully with the value.
cL
N/A
Analog Input
Calibration Status.
Not Searchable/
Configurable
CALIBRATION FAILED (CALIBRATION STATUS)
If the current value input through the analog input
channel is out of the valid range then the device
calibration will fail and the SMART EHO will maintain the
previous calibrated value.
cF
N/A
Analog Input
Calibration Status.
Not Searchable/
Configurable