61
Service Instructions
MAN-02-08-77-0714-EN Rev. 2
September 2020
Section 8: Customizing Smart EHO Settings
Customizing Smart EHO Settings
Table 16.
Configuration Table (5)
MENU NAME
MENU
KEY
CONFIGURATION/
CALIBRATION VALUE
DEFAULT
ACTION
RELAY1 SETTING
Configure Relay1 to provide either a
continuous or flashing signal if Relay1
Function is met. Flashing will be in 1
second intervals.
S1
0 = Continuous
1 = Flashing
0 = Continuous
RELAY2 FUNCTION
Set SMART EHO's configurable relays
to provide various actuator status
indication.
Note: Generic (Host Control) - Host
can activate, deactivate, or control
the relay.
r2
0 = Limit Switch Open (LSO)
1 = Limit Switch Close (LSC)
2 = Limit Switch A (LSA)
3 = Limit Switch B (LSB)
4 = Opening
5 = Closing
6 = Local Mode
7 = Stop Mode
8 = Remote Mode
9 = Valve Drift Alarm
10 = Power Monitor Alarm
11 = Phase Monitor Alarm
12 = Motor Thermal Alarm
13 = Hardwired ESD Alarm
14 = ESD Active Alarm
15 = Lost Analog Input 1 Alarm
16 = Generic (Host Control)
17 = Electronic Fault Alarm
18 = Moving
19 = Valve Stall Alarm
20 = Actuator Fail Alarm
21 = Unit Alarm
22 = SOV Failure Alarm
23 = Hydraulic Circuit Failure Alarm
24 = Self-Calibration Failure Alarm
25 = Over Pressure Alarm
26 = Emergency Stop Alarm
27 = Host Command ESD
1 = Limit
Switch Close
(LSC)