Type 99
2
1. The pressure/temperature limits in this Instruction manual and any applicable standard or code limitation should not be exceeded.
2. For stability or overpressure protection, a pilot supply regulator may be installed in the pilot supply tubing between the main valve and pilot.
3. Type 61LD construction has narrower proportional band than does the standard Type 61L pilot.
4. Type 61LE construction has broader proportional band than does the standard Type 61L pilot.
Specifications
Body Size and End Connection Styles
2-inch (DN 50) body with NPT; CL125, CL150,
CL250, or CL300 flanged; or SWE
Maximum allowable Inlet Pressure
(1)
160 psig (11,0 bar):
When using Type 61LD pilot
400 psig (27,6 bar):
When using Types 61L/
61H pilots
600 psig (41,4 bar):
Type 61HP pilot
(5/8-inch (15,9 mm) orifice maximum)
1000 psig (69,0 bar):
Type 61HP pilot, along with
Type 1301F pilot supply regulator and Type H110
relief valve (1/2-inch (12,7 mm) orifice only)
Outlet (Control) Pressure Ranges
See Table 1
approximate Proportional Bands
See Table 2
Maximum allowable Pressure Drop
(1)
See Table 3
Maximum actuator Pressures
(1)
Operating:
100 psig (6,90 bar)
Emergency:
110 psig (7,58 bar)
Maximum Pilot Spring Case Pressure for
Pressure Loading
(1, 2)
Types 61L, 61LD
(3)
, and 61LE
(4)
:
50 psi (3,45 bar)
with special steel closing cap
Types 61H and 61HP:
100 psi (6,90 bar)
Minimum Differential Pressure Required for
Full Stroke
See Table 3
Maximum Rated Travel
1/4-inch (6,35 mm)
Temperature Capabilities
(1)
With nitrile (nBR) / neoprene (CR):
-20° to 180°F (-29° to 82°C)
With Fluorocarbon (FKM):
0° to 300°F (-18° to 149°C)
PILOT
TyPE
MaXIMUM PILOT
SUPPLy PRESSURE,
PSIg (bar)
OUTLET (COnTROL)
PRESSURE RangES
PILOT COnTROL SPRIng
Part number
Color Code
Wire Diameter,
Inches (cm)
Free Length,
Inches (cm)
61L
400 (27,6)
2 to 4-inches w.c.
3 to 12-inches w.c.
0.25 to 2 psig
1 to 5 psig
2 to 10 psig
5 to 15 psig
10 to 20 psig
(5 to 10 mbar)
(7 to 30 mbar)
(0,02 to 0,14 bar)
(0,07 to 0,34 bar)
(0,14 to 0,69 bar)
(0,34 to 1,03 bar)
(0,69 to 1,38 bar)
1B558527052
1C680627222
1B886327022
1J857827022
1B886427022
1J857927142
1B886527022
Orange
Unpainted
Red
Yellow
Blue
Brown
Green
0.075
0.080
0.109
0.142
0.172
0.187
0.363
(0,19)
(0,20)
(0,28)
(0,36)
(0,44)
(0,47)
(0,92)
4-1/8
3-1/4
2-3/4
2-3/4
2-7/8
2-7/8
3-1/8
(10,5)
(8,26)
(7,00)
(7,00)
(7,30)
(7,30)
(7,94)
61LD
(1)
160 (11,0)
61LE
(2)
400 (27,6)
61H
400 (27,6)
10 to 65 psig (0,69 to 4,48 bar)
0Y0664000A2
Green stripe
0.363
(0,92)
6 (15,2)
61HP
600 (41,4)
35 to 100 psig (2,41 to 6,90 bar)
1D387227022
Blue
0.200
(0,51)
1-11/16
(4,29)
1. Type 61LD construction has narrower proportional band than does the standard Type 61L Pilot.
2. Type 61LE construction has broader proportional band than does the standard Type 61L Pilot.
Table 1.
Outlet Pressure Ranges
PILOT TyPES
PILOT COnTROL SPRIng
PROPORTIOnaL BanDS
Part number
Color Code
Wire Diameter,
Inches (cm)
Free Length,
Inches (cm)
61LD
1B558527052
1C680627222
Orange
Unpainted
0.075 (0,19)
0.080 (0,20)
4-1/8 (10,5)
3-1/4 (8,26)
0.1 to 0.5-inch w.c. (0,25 to 1,0 mbar)
61L
1B886327022
Red
0.109 (0,28)
2-3/4 (7,00)
1 to 2-inches w.c. (2 to 5 mbar)
61LD
1B886327022
Red
0.109 (0,28)
2-3/4 (7,00)
0.25 to 1-inch w.c. (0,62 to 2 mbar)
61LE
1B886327022
Red
0.109 (0,28)
2-3/4 (7,00)
5 to 8-inches w.c. (12 to 20 mbar)
61L, 61LD, 61LE
1B886527022
1J857927142
1B886427022
1J857827022
Green
Brown
Blue
Yellow
0.207 (0,53)
0.187 (0,47)
0.172 (0,44)
0.142 (0,36)
3-1/8 (7,94)
2-7/8 (7,30)
2-7/8 (7,30)
2-3/4 (7,00)
0.1 to 0.3 psi (0,007 to 0,02 bar)
61H
0Y0664000A2
Green stripe
0.363 (0,92)
6 (15,2)
0.1 to 0.3 psi (0,007 to 0,02 bar)
61HP
1D387227022
Blue
0.200 (0,51)
1-11/16 (4,29)
1 to 2 psi (0,069 to 0,14 bar)
Table 2.
Proportional Bands