Rosemount Model 8800C Vortex Flowmeter
3-8
Density Ratio
Density Ratio is used to convert actual volumetric flow to standard
volumetric flow rates based on the following equations:
Calculate Density Ratio
Calculate Density Ratio will calculate the density ratio (shown
above) based on user entered process and base conditions.
Operating Conditions
T
f
= absolute temperature at actual (flowing) conditions in degrees
Rankine or Kelvin. (The transmitter will convert from degrees
Fahrenheit or degrees Celsius to degrees Rankine or Kelvin
respectively.)
P
f
= absolute pressure at actual (flowing) conditions psia or KPa
absolute. (The transmitter will convert from psi, bar, kg/sqcm, kpa, or
mpa to psi or kpa for calculation. Note that pressure values must be
absolute.)
Z
f
= compressibility at actual (flowing) conditions (dimensionless)
Base Conditions
T
b
= absolute temperature at standard (base) conditions degrees Rankine
or Kelvin. (The transmitter will convert from degrees Fahrenheit or
degrees Celsius to degrees Rankine or Kelvin respectively.)
P
b
= absolute pressure at standard (base) conditions psia or KPa
absolute. (The transmitter will convert from psi, bar, kg/sqcm, kpa, or mpa
to psi or kpa for calculation. Note that pressure values must be absolute.)
Z
b
= compressibility at standard (base) conditions (dimensionless)
Example
Configure the Model 8800C to display flow in standard cubic feet per
minute (SCFM). (Fluid is hydrogen flowing at conditions of 170 °F and
100 psia.) Assume base conditions of 59 °F and 14.696 psia.)
HART Comm.
1, 3, 3, 3, 2
HART Comm.
1, 3, 3, 3, 3
HART Comm.
1, 3, 3, 3, 3, 1
HART Comm.
1, 3, 3, 3, 3, 2
Conversion factor
density at actual (flowing) conditions
density at s
dard (base)
tan
conditions
------------------------------------------------------------------------------------------------------------
=
Conversion factor
T
b
P
f
Z
b
T
f
P
b
Z
f
-------------------------------
=
Conversion factor
518.57 °R
100 psia
1.0006
629.67 °R
14.7 psia
1.0036
-----------------------------------------------------------------------------------
5.587
=
=
Summary of Contents for 8800A
Page 1: ...Model 8800C and Model 8800A Smart Vortex Flowmeter 00809 0100 4003 English Rev JA ...
Page 2: ......
Page 4: ...Rosemount Model 8800C Vortex Flowmeter ...
Page 8: ...Rosemount Model 8800C Smart Vortex Flowmeter 4 ...
Page 10: ...Rosemount Model 8800C Vortex Flowmeter 1 2 ...
Page 48: ...Rosemount Model 8800C Vortex Flowmeter 2 38 ...
Page 74: ...Rosemount Model 8800C Vortex Flowmeter 3 26 ...
Page 102: ...Rosemount Model 8800C Vortex Flowmeter 4 28 ...
Page 128: ...Rosemount Model 8800C Vortex Flowmeter B 2 ...
Page 129: ...B 3 Approvals ...
Page 130: ...Rosemount Model 8800C Vortex Flowmeter B 4 ...
Page 131: ...B 5 Approvals ...
Page 132: ...Rosemount Model 8800C Vortex Flowmeter B 6 ...
Page 133: ...Appendix C 1 Appendix C HART Communicator Connections and Hardware page C 6 ...
Page 142: ...Rosemount Model 8800C Vortex Flowmeter C 10 ...
Page 159: ......