2-37
Installation
Use the following steps to install the transient protector:
1. If the flowmeter is installed in a loop, secure the loop and
disconnect power.
2. Remove the field terminal side flowmeter cover.
3. Remove the captive screws.
4. Use pliers to pull the terminal block out of the housing.
5. Inspect the connector pins for straightness.
6. Place the new terminal block in position and carefully press it into
place. The terminal block may have to be moved back and forth to
get the connector pins started into the sockets.
7. Tighten the captive screws.
8. Install and tighten the ground screw.
Figure 2-28. The Transient Terminal Block
9. Replace the cover.
Transient Terminal
Block Ground screw
Captive Screws
Housing Ground
8
800
-0
0
00A
03D
Summary of Contents for 8800A
Page 1: ...Model 8800C and Model 8800A Smart Vortex Flowmeter 00809 0100 4003 English Rev JA ...
Page 2: ......
Page 4: ...Rosemount Model 8800C Vortex Flowmeter ...
Page 8: ...Rosemount Model 8800C Smart Vortex Flowmeter 4 ...
Page 10: ...Rosemount Model 8800C Vortex Flowmeter 1 2 ...
Page 48: ...Rosemount Model 8800C Vortex Flowmeter 2 38 ...
Page 74: ...Rosemount Model 8800C Vortex Flowmeter 3 26 ...
Page 102: ...Rosemount Model 8800C Vortex Flowmeter 4 28 ...
Page 128: ...Rosemount Model 8800C Vortex Flowmeter B 2 ...
Page 129: ...B 3 Approvals ...
Page 130: ...Rosemount Model 8800C Vortex Flowmeter B 4 ...
Page 131: ...B 5 Approvals ...
Page 132: ...Rosemount Model 8800C Vortex Flowmeter B 6 ...
Page 133: ...Appendix C 1 Appendix C HART Communicator Connections and Hardware page C 6 ...
Page 142: ...Rosemount Model 8800C Vortex Flowmeter C 10 ...
Page 159: ......