EES-101 Series Ultrasonic Flowmeter
Revision: 3.0.1
Page 32 of 65
Serial Port Settings (Title: RS485 Setup)
This window is used for serial port setting. Serial port
is used to communicate with other instruments. The
serial port parameters setting of the instrument that
applies the serial port connection must be consistence.
The first selected data indicates baud rate, 4800, 9600,
14400, 19200, 38400, 43000, 57600, 76800, 115200
are available.
The second option indicates parity bit, None (No
verification).
Data length fixed to 8;
Stop bit length for a fixed length.
The factory default serial port parameter is "9600,
None".
FO Frequency Range
Set the highest limit of the output signal frequency.
highest limit frequency values must be greater than
the lower frequency range
:
0~9999Hz
,
Factory default
:
0~5000Hz.
Note: output frequency signal output from OCT
mouth, so to output frequency signal, must also Be set
OCT into frequency signal output mode
(
M78 choose
0. FO).
Low FO Flow Rate
Set up low FO flow rate, i.e. the corresponding flow
value when output signal frequency is at the lowest
FO frequency. For example, when the low FO
frequency is 1000 Hz, low FO flow rate is 100m3/h
then when the frequency output is 1000 Hz, the low
flow at this moment measured by the Flowmeter is
100m3/h.
High FO Flow Rate
Enter the high FO flow rate, i.e. the corresponding
flow value when frequency output signal is at highest
FO frequency. For example, when the low FO
frequency is 5000Hz, low FO flow rate is
1000m3/h,then when the frequency output is 5000Hz,
the low flow at this moment measured by the
Flowmeter is 1000m3/h.
Menu
6
2
RS485 Setup [62
1 . 9600 None
Menu
6
7
FO Frequency Range
1
-
5000
Menu
6
8
Low FO Flow Rate [68
0 m3/h
Menu
6
9
High FO Flow Rate [69
26550 m3/h