12
3.2: Vent Pipe Spacing for Multiple Peak Boilers
7. Sidewall Venting Configuration:
a. See Figure 3.3 for an illustration of clearances for
location of exit terminals of direct-vent venting systems.
• This boiler vent system shall terminate at least 3 feet
(0.9 m) above any forced air inlet located within 10
ft (3 m). Note: This does not apply to the combustion
air intake of a directvent appliance.
• Provide a minimum of 1 foot (30 cm) distance from
any door, operable window, or gravity intake into
any building.
• Provide a minimum of 1 foot (30 cm) clearance from
the bottom of the exit terminal above the expected
snow accumulation level. Snow removal may be
required to maintain clearance.
• Provide a minimum of 4 feet (1.22 m) horizontal clearance
from electrical meters, gas meters, gas regulators, and relief
equipment. In no case shall the exit terminal be above or
below the aforementioned equipment unless the 4 foot
horizontal distance is maintained.
• Do not locate the exhaust exit terminal over public
walkways where condensate could drip and create a
hazard or nuisance.
• When adjacent to public walkways, locate the exit
terminal at least 7 feet above grade.
• Do not locate the exhaust termination directly under
roof overhangs to prevent icicles from forming or
recirculation of exhaust gases from occurring.
• Provide 3 feet clearance from the inside corner of
adjacent walls.
b. Figures 3.4 through 3.7 show approved sidewall venting
configurations using the standard fittings supplied.
c. Figure 3.5 is only approved for locations in which the
outdoor temperature is above -5°F (-21°C) in accordance
with ASHRAE 90A-1980 recommendations.
VENTING & AIR INLET PIPING
CAUTION
Condensing flue gases can freeze on exterior
building surfaces which may cause discoloration and
degradation of the surfaces.
Figure 3.4: Standard Exhaust & Air Inlet Pipe
Terminations
Figure 3.5: Offset Exhaust and Air Inlet Terminations
Summary of Contents for Peak-40
Page 22: ...22 WATER PIPING AND CONTROLS Figure 4 6 Recommended Central Heat Piping ...
Page 24: ...24 WATER PIPING AND CONTROLS Figure 4 8 Recommended Domestic Hot Water Piping ...
Page 33: ...33 ELECTRICAL CONNECTIONS Figure 7 4 Wiring Schematic and Connection ...
Page 47: ...47 START UP PROCEDURE E LIGHTING OPERATING PROCEDURES ...
Page 59: ...59 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 62: ...62 REPAIR PARTS Figure 13 2 Peak 40 LP Combustion Components ...
Page 64: ...64 REPAIR PARTS Figure 13 3 Peak 40 NG Combustion Components ...
Page 66: ...66 REPAIR PARTS Figure 13 4 CHB Parts Detail ...
Page 68: ...315 Oser Avenue Hauppauge NY 11788 Tel 631 694 1800 Fax 631 694 1832 www embassyind com ...