10 .7 .2 Relief valve (VPS)
Parameter 52
One of the valves connected to terminal 14, 15 or 57 can be
selected to discharge the test volume during a tightness test.
V2
V3
V4
PZ
µC
VAS
p
u
/2
14 15
13
45
52
55
54
53
56
57
38
37
18
17
V
p1
V2
V3
V4
14 15 57
Parameter 52 = 2: V2. The test volume is discharged via the
valve connected to terminal 14.
Parameter 52 = 3: V3. The test volume is discharged via the
valve connected to terminal 15.
Parameter 52 = 4: V4. The test volume is discharged via the
valve connected to terminal 57.
10 .7 .3 Measurement time V
p1
Parameter 56
The required measurement time must be determined ac-
cording to the requirements of the appropriate application
standards, e.g. EN 1643.
BCU 56x..C1
µC
P
13
14
45
p
u
/2
TC
PZ
>750°
ϑ
1
2
3
p
u
/2
PZ
V
p1
V1
V2
The required measurement time for the tightness test of V
p1
can be set using parameter 56. The possible settings are 3 s,
5 to 25 s (in 5 s steps) or 30 to 3600 s (in 10 s steps).
See also page 30 (Measurement time tM).
Parameters > Valve check