BCU 580 · Edition 11.15
11
1 .1 .4 Modulating-controlled burner
Control:
Main burner continuous
The butterfly valve for air is moved to the
position for minimum capacity in order to
start the main burner. The main burner
is started with minimum capacity after
the operating signal from the pilot burner
has been detected. The control system
controls the burner capacity via the but-
terfly valve for air after the operating
state has been signalled. Pilot and main
burners can be operated simultaneously.
This reduces the time required by the
main burner for starting up.