BCU 580 · Edition 11.15
40
“Burner 1 flame signal” module (device
➔
controller) – slot 2
The flame signal for burner 1 is transferred from the BCU to
the PLC as an analogue value using this module. The flame
signal occupies one byte with values from 0 to 255 (= flame
signal from 0 to 25.5 µA).
Bit Byte n
Data type Format
Value
0
Burner 1 flame signal
Byte
DEC
0 – 255
(0 – 25.5 μA)
1
2
3
4
5
6
7
“Burner 2 flame signal” module (device
➔
controller) – slot 3
The flame signal for burner 2 is transferred from the BCU to
the PLC as an analogue value using this module. The flame
signal occupies one byte with values from 0 to 255 (= flame
signal from 0 to 25.5 µA).
Bit Byte n
Data type Format
Value
0
Burner 2 flame
signal
Byte
DEC
0 – 255
(0 – 25.5 μA)
1
2
3
4
5
6
7
“Status signal” module (device
➔
controller) – slot 4
This module transfers the status signals from the BCU to
the PLC. The status signals occupy one byte (0 to 255). Every
status signal is allocated a code. The allocation is described
in the code table “GSD Codes BCU 580”.
Bit Byte n
Data
type
Format
Value
0
Status signals
Byte
DEC
0 – 255
(see
Code table “GSD_
Codes_BCU580.xlsx”
at
www.docuthek.com)
1
2
3
4
5
6
7
Profinet > GSD file for PLC configuration > Modules for cyclic data exchange
▼