12 .3 .2 Safety current inputs
Actuation of the safety current inputs only with switchgear fea-
turing mechanical contacts. If switchgear with semi-conductor
contacts is used, the safety current inputs must be connected
using relay contacts.
To safeguard the safety current inputs, the fuse must be de-
signed so that the sensor with the lowest switching capacity
is protected.
The cabling outside enclosed installation spaces must be
protected from mechanical damage and stress (e.g. vibration
or bending) as well as short-circuits, short-circuits to ground
and cross-circuits.