Volume Conversion Device EK260
44
Elster GmbH
3.7.1 List of status messages
Message
in status
AD
Description
1
StSy
SRSy
Restart
Restart of the device
1
St.5
SR.5
C-fact. err.
Conversion factor cannot be computed
1
St.6
SR.6
T Alarm Lim.
Alarm limits for temperature violated
1
St.7
SR.7
p Alarm Lim.
Alarm limits for pressure violated
1
St.8
SR.8
K-val. error
Compressibility cannot be computed
1
St.9
SR.9
Z-fact. err.
Compressibility factor cannot be computed
2
St.1
SR.1
I1 Alarm
Alarm on Input I1
2
St.5
SR.5
T Inp. Error
No usable input value for temperature
A
la
rm
1
2
St.6
SR.6
p Inp. error
No usable input values for pressure
3
StSy
SRSy
Data restore
Data has been restored
4
St.1
SR.1
Outp.1 Error
Error on Output 1
4
St.2
SR.2
Outp.2 error
Error on Output 2
4
St.3
SR.3
Outp.3 error
Error on Output 3
4
St.4
SR.4
Outp.4 error
Error on Output 4
5
St.2
SR.2
I2 Pulse cmp
Error during pulse comparison on Input 2
6
St.1
SR.1
W Warn Lim.
Warning limits for power violated
6
St.2
SR.2
Vb Warn Lim.
Warning limits for flow at base cond. violated
6
St.4
SR.4
Vm Warn Lim. Warning limits for actual flow violated
6
St.6
SR.6
T Warn Lim.
Warning limits for temperature violated
6
St.7
SR.7
p Warn Lim.
Warning limits for pressure violated
7
StSy
SRSy
Soft. error
Software error
8
StSy
SRSy
Sett. error
Setting error
8
St.2
SR.2
I2 Warn.sig.
Warning signal on Input I2
W
a
rn
in
g
2
8
St.3
SR.3
I3 Warn.sig.
Warning signal on Input I3
9
StSy
.
Batt. low
Battery service life below limit
10
StSy
.
Repair mode
Repair mode switched on
11
StSy
.
Clock n. set
Clock not set
11
St.1
.
Encoder err.
Encoder error
12
StSy
.
PLogb full
Calibration logbook full
13
StSy
.
online
Data transmission running
13
St.2
.
I2 Rep.sig.
Report signal on Input I2
13
St.3
.
I3 Rep.sig.
Report signal on Input I3
14
StSy
.
Remote clock
Remote clock setting started
14
St.1
.
Cal.lock o.
Calibration lock open
14
St.2
.
Man.lock o.
Manufacturer's lock is open
14
St.3
.
Supp.lock o.
Supplier's lock is open
14
St.4
.
Cust.lock o.
Customer's lock is open
15
StSy
.
Batt. operat
Battery operation
15
St.1
.
Call Win.1+
Extended Call acceptance time window 1
16
StSy
.
Dayl.Sav.Tim
The displayed time is daylight saving time
16
St.1
.
Call Win.1
Call acceptance time window 1 is active
R
e
p
o
rt
3
16
St.2
.
Call Win.2
Call acceptance time window 2 is active
1
Alarm: Instead of the act. measurement, the substitute value is used; quantities are
counted in the disturbance volume counter.
2
Warning: The message is held in the status register until manually deleted.
3
Report: The message is not kept in the status register.
Summary of Contents for 83 462 140
Page 117: ...Volume Conversion Device EK260 Elster GmbH 117 A 2 Approval for Ex Zone 1 ...
Page 118: ...Volume Conversion Device EK260 118 Elster GmbH ...
Page 119: ...Volume Conversion Device EK260 Elster GmbH 119 ...
Page 120: ...Volume Conversion Device EK260 120 Elster GmbH ...
Page 121: ...Volume Conversion Device EK260 Elster GmbH 121 ...