Volume Conversion Device EK260
28
Elster GmbH
3.3 Pressure list
AD
Designation / value
Unit
Access Address DC
p
Pressure
bar
-
7:310_1 4
p.LW
Lower warning limit pressure
bar
S
10:150
8
p.UW
Upper warning limit pressure
bar
S
10:158
8
pMin
Lower alarm limit pressure
bar
C
7:3A8_1 8
pMax
Upper alarm limit pressure
bar
C
7:3A0_1 8
MRL.p
Pressure meas. range lower limit
bar
C
6:224_1 8
MRU.p
Pressure meas. range upper limit
bar
C
6:225_1 8
p.F
Pressure substitute value
bar
S
7:311_1 8
pb
Pressure at base conditions
bar
C
7:312_1 8
Md.p
Pressure mode
-
C
7:317
7
Typ.p
Pressure sensor type
-
C
6:223
8
SNp
Serial no. of pressure sensor
-
C
6:222
8
Eq1p
Coefficient 1 of pressure equation
-
C
6:280
8
Eq2p
Coefficient 2 of pressure equation
-
C
6:281
8
Eq3p
Coefficient 3 of pressure equation
-
C
6:282
8
p1Adj
Adjustment value 1 for pressure
bar
C
6:260_1 8
p2Adj
Adjustment value 2 for pressure
bar
C
6:261_1 8
Prog
Accept pressure adjustment
-
C
6:259
2
p.Amb
Air pressure fixed value
bar
C
6:212_1 8
p.Mes
Pressure meas.
bar
-
6:211_1 4
p.Abs
Absolute pressure measurement
bar
-
6:210_1 4
p.MP
Ø
Measurement period mean pressure
bar
-
19:160 16
p.Mon max Month's maximum pressure
bar
-
21:160 16
p.Mon min Month's minimum pressure
bar
-
22:160 16
(Legends: see page 22)
p
Press.
p
is the pressure which is used for computing the conversion factor (
→
3.5) and
hence the volume at base conditions (
→
3.1).
In disturbance-free operation the measurement
p.Abs
(see below) is used:
p
= p.Abs.
With a relevant disturbance (alarm), the substitute value
p.F
(see below) is used:
p
=
p.F
. In addition, disturbance quantities are then counted (
→
3.1, 3.2) and the
message "p Alarm Lim." displayed (
→
page 45 ). Relevant disturbances are:
−
p.Abs
is located outside of the set limits
pMin
and
pMax
(see below).
−
With a connected encoder (Md.I1 = 5,
→
3.10) no actual volume can be
measured for more than 20 seconds. Since the gas flow variation is not known
for the time period and therefore no gas quantities can be assigned to the
measured values of pressure and temperature, the correction occurs as
disturbance quantities with substitute values for pressure and temperature.
(
→
4.5)
Summary of Contents for 83 462 140
Page 117: ...Volume Conversion Device EK260 Elster GmbH 117 A 2 Approval for Ex Zone 1 ...
Page 118: ...Volume Conversion Device EK260 118 Elster GmbH ...
Page 119: ...Volume Conversion Device EK260 Elster GmbH 119 ...
Page 120: ...Volume Conversion Device EK260 120 Elster GmbH ...
Page 121: ...Volume Conversion Device EK260 Elster GmbH 121 ...