Fixed Quality vs. Fixed Ratio
The most important parameter defining the actual compression ratio, (which determines the amount
of storage required and maximum time continuous data can be stored) is a PQZIP Threshold value or
Tolerance
as it referred on the WEB page. The Tolerance defines what change in an individual
harmonic would be defined as significant enough to be stored and reproduced afterwards.
The tolerance value is calculated in percentage to the full scale or nominal reading for the specific
channel. It is assumed that changes within 0.1% of nominal would have no importance in further
power quality investigation, and the values within that range are averaged to store the
representative value only. The basic and factory default tolerance value is normally defined as
0.1%. However, on some sites/networks that value can still be considered too low, for example, a
highly fluctuating load or voltage lines. It is most likely that a user would prefer increasing a
tolerance value for currents or voltages or even both in order to achieve better compression ratios
on highly polluted network locations.
Configuring fixed ratio:
The Portable BLACKBOX provides the possibility of automatic adjustment of the actual tolerance
value presuming a compression ratio defined as amount of data being stored per month. This option
is called
Fixed Ratio
. When selected, the user is requested to define the amount of data to be
stored per month (
Monthly Ratio
) in
MB.
Usually, slight voltage spectral changes have higher
importance than current changes. Therefore, the amount of data which could be stored for voltages
may be determined as greater than for currents. The
V/I Relation
parameter defines the
relationship between the data (a part of the Monthly Ratio) reserved for voltage. If the voltage
portion is larger than currents, the system will define a tighter tolerance for voltages than for
currents.
Access your Portable BLACKBOX Unit's PQZIP Configuration via the
In the
PQZIP Configuration
section, go to the
PQZIP Mode
& from the drop-down selection
select
Fixed Ratio
followed by
.
The
PQZIP Configuration
window will now
open
:
Define the amount of data stored per month, by entering the
MB Value
in the
Monthly Ratio
text box
Set the appropriate
V/I Relation
value with the
To apply your changes select
Summary of Contents for G3500 BlackBox
Page 1: ...1 ...
Page 38: ...38 2Phase TR SINGLE SPLIT PHASE delta 3 wires THREE WIRE DELTA ...
Page 39: ...39 delta 3 wires Grounded Delta wye 4 wires four wire wye ...
Page 40: ...40 wye 4 wires three wire wye Delta 3 wires delta high leg ...
Page 82: ...82 The Average Window will now open ...
Page 96: ...96 The Waveforms Window will now open ...
Page 113: ...113 Export Dialog Various Export Options ...
Page 130: ...130 The window containing the table for V I Min Max Harmonics values will now open ...
Page 171: ...171 SEE ALSO About Energy Measurement Status ...
Page 207: ...207 SEE ALSO About the Current Window Current Probes Info Non Measured Currents ...
Page 217: ...217 Open the LAN Tab Select or complete the following in the applicable sections select ...
Page 220: ...220 You should now be able to identify the Router on your computer s Network Sharing Center ...
Page 247: ...247 ...
Page 327: ...327 SEE ALSO About BLACKBOX s Communication Configuration Security Network Serial Ports ...
Page 331: ...331 SEE ALSO About BLACKBOX s Communication Configuration Security Network Serial Ports ...
Page 334: ...334 SEE ALSO About Battery Replacement G3500 BLACKBOX Unit G4500 BLACKBOX Unit ...
Page 357: ...357 DIMENSIONAL VIEW G4500 ...
Page 358: ...DIMENSIONAL VIEW G3500 SEE ALSO G4500 G3500 Specifications ...