background image

7

Transfer protocol

KNX B4 Universal Interface

 • Version: 13.09.2021 • from application 1.0 • Technical changes and errors excepted.

5.

Transfer protocol

5.1. List of all communication objects

Abbreviations:

R

Read

W Write
C

Communication

T

Transmit

U

Update

DPT Data Point Type

No.

Name

Function

Description

Lenght

DPT

Flags

0

Dimming 
on/off

Input A/B

This object is used to switch 
on/off a dimmable light 
source (two-button 
dimming).

1 bit

DPT1

CR-T-

0

Sun 
protec-
tion up/
down

Input A/B

This object is used to move 
the shutter(s) up or down 
(two-button shutter).

1 bit

DPT1

CR-T-

0

Switch

Input A

This object is used to switch 
on/off, to toggle or to "send 
status".

1 bit

DPT1

CR-T-

0

Switch 
short

Input A

This object is used to switch 
on/off or to toggle on a 
short button press.

1 bit

DPT1

CR-T-

0

Counter 
reset

Input A

This object is used to reset 
the counter on receiving a 
telegram with "0" or "1".

2 bit,
1 byte, 
2 bytes

DPT1

CR-T-

0

Send 
value

Input A

This object is used to send a 
predefined value on a short 
button press.

1 bit

DPT2, 
DPT5, 
DPT7, 
DPT9

C-W-U

0

Dimming 
on/off

Input A

This object is used to switch 
on/off a dimmable light 
source (one-button 
dimming).

1 bit

DPT1

CR-T-

0

Sun 
protec-
tion up/
down

Input A

This object is used to move 
the shutter(s) up or down 
(one-button shutter).

1 bit

DPT1

CR-T-

1

Dimming

Input A/B

This object is used to dim 
brighter or darker (two-
button dimming).

1 byte

DPT3

CR-T-

Summary of Contents for 70251

Page 1: ...EN Installation and Adjustment KNX B4 Universal Interface Item number 70251 ...

Page 2: ......

Page 3: ...e device at the bus 4 4 Operation 4 4 1 Binary Input Application 5 4 2 Programming 5 4 2 1 Programming of Individual Address and Application 5 5 Transfer protocol 7 5 1 List of all communication objects 7 6 ETS Database Parameters 13 6 1 General 13 6 2 Channel A B C D 13 6 2 1 Switch 13 6 2 2 Scene 14 6 2 3 Counter 15 6 2 4 Send value 16 6 2 5 One button dimming 17 6 2 6 One button shutter 18 6 3 ...

Page 4: ...in this manual Safety advice Safety advice for working on electrical connections components etc DANGER indicates an immediately hazardous situation which will lead to death or severe injuries if it is not avoided WARNING indicates a potentially hazardous situation which may lead to death or severe injuries if it is not avoided CAUTION indicates a potentially hazardous situation which may lead to t...

Page 5: ...nd only in the sur roundings designated for it Elsner Elektronik is not liable for any changes in norms and standards which may occur after publication of these operating instructions For information on installation maintenance disposal scope of delivery and technical data please refer to the installation instructions 2 Description The KNX B4 Universal Interface is a 4 fold KNX binary input to sen...

Page 6: ...wo button dimming Switch short long button press Scene 8 bit with without saving function 1 bit Counter 8 bit 16 bit 32 bit Send value percent angle temperature 2 bit 8 bit 16 bit Push button for programming the Individual Address Can be used with ETS 3 0d and higher 3 Commissioning Configuration is made using the KNX software as of ETS 3 0d The product file can be downloaded from the ETS online c...

Page 7: ...ounter 8 bit 16 bit 32 bit Send value Percent Angle Temperature 2 bit 8 bit 16 bit One button dimming One button shutter To reset an input channel s counter a telegram containing 0 or 1 must be received by the corresponding communication object Counter reset 4 2 Programming 4 2 1 Programming of Individual Address and Application To download Individual Address and or ETS application the Programming...

Page 8: ...6 Operation KNX B4 Universal Interface Version 13 09 2021 Technical changes and errors excepted Fig 1 ETS Properties Window ...

Page 9: ...ject is used to switch on off to toggle or to send status 1 bit DPT1 CR T 0 Switch short Input A This object is used to switch on off or to toggle on a short button press 1 bit DPT1 CR T 0 Counter reset Input A This object is used to reset the counter on receiving a telegram with 0 or 1 2 bit 1 byte 2 bytes DPT1 CR T 0 Send value Input A This object is used to send a predefined value on a short bu...

Page 10: ...er 1 bit DPT1 C WTU 2 Scene Input A This object is used to recall or learn the configured 8 bit scene 1 64 1 byte DPT18 CR T 2 1 bit Scene Input A This object is used to recall or learn the configured 1 bit scene 1 or 2 1 bit DPT1 CR T 3 Counter Input A This object is used as counter 8 bit 16 bit or 32 bit for rising edge falling edge or both edges 1 byte 2 bytes 4 bytes DPT5 DPT7 DPT12 CRWTU 4 In...

Page 11: ...edefined value on a long button press 2 bit 1 byte 2 bytes DPT2 DPT5 DPT7 DPT9 CR T 6 Dimming Input B This object is used to dim brighter or darker one button dimming 1 bit DPT3 CR T 6 Blinds open close Input B This object is used to stop movement and adjust the blinds one button shutter 4 bit DPT1 CR T 7 Scene Input B This object is used to recall or learn the configured 8 bit scene 1 64 1 byte D...

Page 12: ...immable light source one button dimming 1 bit DPT1 CR T 10 Sun protec tion up down Input C This object is used to move the shutter s up or down one button shutter 1 bit DPT1 CR T 11 Dimming Input C D This object is used to dim brighter or darker two button dimming 4 bit DPT3 CR T 11 Blinds open close Input C D This object is used to close or open the blinds two button shutter 1 byte DPT1 CR T 11 S...

Page 13: ...CR T 15 Switch short Input D This object is used to switch on off or to toggle on a short button press 1 bit DPT1 CR T 15 Counter reset Input D This object is used to reset the counter on receiving a telegram with 0 or 1 1 bit DPT1 C W U 15 Send value Input D This object is used to send a predefined value on a short button press 2 bit 1 byte 2 bytes DPT2 DPT5 DPT7 DPT9 CR T 15 Dimming on off Input...

Page 14: ...7 Counter limit Input D This object is used to recall or learn the configured 8 bit scene 1 64 1 byte DPT1 CR T 17 1 bit Scene Input D This object is used to recall or learn the configured 1 bit scene 1 or 2 1 bit DPT1 CR TU 18 Counter Input D This object is used as counter 8 bit 16 bit or 32 bit for rising edge falling edge or both edges 1 byte 2 bytes 4 bytes DPT5 DPT7 DPT12 CRWTU 19 Interlock I...

Page 15: ...iple operation of the inputs e g due to bouncing of the contact It applies to all four channels Function channels A B not active single channels Dimming Shutter Configuration of input channels A B Function channels C D not active single channels Dimming Shutter Configuration of input channels C D Function inactive Switch Counter Send value One button dimming One button shutter Functions that can b...

Page 16: ...ue short press nothing off on if contact is opened or closed The here defined action is executed after a short button press available for switch on short long button press Value long press nothing off on if contact is opened or closed The here defined action is executed after a long button press available for switch on short long button press Long button press after 0 3 30 0 s 2 0 s Duration that ...

Page 17: ... be sent available for Switch short long Scene Scene 1 Scene 2 One of 2 possible 1 bit scenes can be recalled available for 1 bit Interlock disabled enabled If Interlock is active changes at the Input are not considered until the Interlock is deacti vated again Count edge rising edge falling edge both edges Defines on which edge s the counter is increasing Contact type normally open normally close...

Page 18: ...ines the contact type at the input NO or NC If NO is selected the input is logic high after the contact is closed Value type Percent Angle Temperature 2 bit value forced operation 8 bit value 16 bit value Sets the type of value Value rising edge Percent 0 100 Angle 0 5 10 360 Temperature x 100 C 27300 32000 0 2 bit ON activate forced operation OFF activate forced operation deactivate forced operat...

Page 19: ... 2 bit ON activate forced operation OFF activate forced operation deactivate forced operation 8 bit 0 65535 16 bit 0 65535 Sets value available for on short long button press and on long button press Long button press after 0 3 30 0 s 2 0 s Time the input needs to be logical high to start the long operation If the input is logical high for a shorter time only the command for short operation will b...

Page 20: ...ng Contact type normally open normally closed Defines the contact type at the input NO or NC If NO is selected the input is logic high after the contact is closed Long button press after 0 3 30 0 s 2 0 s Time the input needs to be logical high to start the long operation If the input is logical high for a shorter time only the command for short operation will be sent Interlock disabled enabled If ...

Page 21: ...ly open normally closed Defines the contact type at the input NO or NC If NO is selected the input is logic high after the contact is closed Shutter function A B up down down up Defines the inputs for moving the shutter up and for moving the shutter down up down Channel A moves the shutter up Channel B moves the shutter down down up Channel A moves the shutter down Channel B moves the shutter up L...

Page 22: ...mbH Control and Automation Engineering Sohlengrund 16 75395 Ostelsheim Phone 49 0 70 33 30 945 0 info elsner elektronik de Germany Fax 49 0 70 33 30 945 20 www elsner elektronik de Technical support 49 0 70 33 30 945 250 ...

Reviews: