MISSION 1K●2K●3K
SINGLE PHASE
Rev. 02
– 19 March 2015
15
3
Confirm the auto battery test setting interface. After selecting ON or OFF, press and hold the function
setting key
for more than half a second (less than 2 seconds), Now, the ABT setting function is
completed and the “ON” or “OFF” below the “ABT” will light without flash.
4
Exit from the setting interface. Press and hold function setting key
for more than 2 seconds, exit from
the setting interface and return to main interface.
5
When the ABT function is set to ON , the UPS will automatically do battery test every 30 days for 10
seconds if utility is available
4.3.8
Warning Code function setting (wc)
1
To enter the configuration interface, press and hold the configuration function key
for more than 2
seconds, then access the configuration interface. Press the key
until you reac
h the “wc” (8) menu, the
word "wc" flashes:
2
Start the Warning Code selection interface: Press and hold the configuration function key
for
more than half second (less than 2 seconds), enter the configuration wc interface, at this point the wc
will remain fixed and the word "ON" (or OFF) under wc will flash. Press the key
to select ON or
OFF.
3
Confirm the wc selection interface: after selecting ON or OFF, pressing and holding the configuration
function key
for more than half a second (less than 2 seconds) confirms the selection. Now, the
configuration of the wc function is completed and the word "ON" or "OFF" under "wc" will remain fixed.
4
Exit the configuration interface. Press and hold the configuration function key
for more than 2
seconds to exit this configuration interface and return to the main interface.
5
When the wc function is set to ON, the Ups will show cyclically (2 ~ 5 sec) any alarm messages. For
alarm messages refer to the table in Appendix1.
4.3.9
Emergency Power Off polarity function setting (EPO)
1
To enter the Configuration Interface, press and hold the Configuration Function key
for more than
2 seconds, then access the Configuration Interface. Press the key
until you reach the EPO menu
(9), the word "EPO" flashes:
2
Start the EPO selection interface: press and hold the configuration function key
for more than half
second (less than 2 seconds), enter the EPO Configuration Interface, then "EPO" will remain fixed and
the word "- P" under EPO will blink. Press the key
to select "- P" or "+ P".
3
Confirm EPO Selection Interface: After selecting "- P" (short circuit executes EPO function) or "+ P"
(open circuit performs EPO function), holding the configuration function key
more than half