background image

Technical Manual MSR Universal Stage Controller

Page 7

Stage Cont Pressure Transmitter (Compressors)

The control setpoint is preset by P04 as a pressure value.
There is no need for an access code. The hysteresis P10 is
located symmetrical around the control setpoint.

Forward (Stages on)

If the measured pressure value exceeds the setpoint (P04
plus ½
  P10  (hysteresis), the forward delay P20 will be
started. After this timer is run down, a stage will be switched
ON and the timer starts again. Read at P33 if a delay time is
still running and when a stage will be switched on or off.

Neutral zone

If the actual pressure value is located within the limits set by
P10 (hysteresis, located around the setpoint), then no stage
will be activated or de-activated.

Backrun (Stages will be switched off)

If the actual pressure value falls short of P04 minus ½ P10,
the backrun delay P21 will be started. After this timer is run
down, one stage will be switched off, the timer starts again,
and so on.

Stage Controller

The control characteristic of the stages differ depending on the
operating mode and the selected sensors (P28).
To prevent that the final user adjusts the setpoints to an inadmis-
sible value, the setpoint range can be limited by P08 and P09.

Stage Cont Pressostat (Compressors or Fans)

The MSR gets the Forward/Backrun informations from a
Pressostat (or another potential free contact).
Functions depending on analog informations are not availa-
ble if this sensor is selected.

Forward (Stages on)

If the Pressostat is switched to 'Forward', the forward delay
P20 will be started. After this timer is run down, a stage will
be switched ON and the timer starts again. Read at P33 if a
delay time is still running and when a stage will be switched
on or off.

Neutral zone

If the contacts of the Pressostat are open (mid position), then
no stage will be activated or de-activated.

Backrun (Stages will be switched off)

If the Pressostat is switched to 'Backrun', the backrun delay
P21 will be started. After this timer is run down, one stage will
be switched off, the timer starts again, and so on.

Stage Controller for Brine-Chillers

The control setpoint is pre-
set by P04 as a tempera-
ture value (this is the set-
point for stage 1 at the
same time). There is no
need for an access code.
The following stages
switch in a distance to the
previous stage (P05, P06, P07). The
hysteresis P10 is located symmetrical around the setpoints.

Forward (Stages on)
If the measured temperature value exceeds one of the
setpoints (P04 - P07) plus ½ P10 (hysteresis), the forward
delay  P20 will be started. After this timer is run down, the
corresponding stage will be activated and the timer starts
again. Read at P33 if a delay time is still running and when
a stage will be switched on or off.

Neutral zone
If the actual value is located within the limits set by P10
(hysteresis, located around all setpoints), then no stage will
be activated or de-activated.

Backrun (Stages will be switched off)
If the actual temperature value falls short of a setpoint - ½
P10
, the backrun delay P21 will be started. After this timer is
run down, the corresponding stage will be switched off, the
timer starts again, and so on.

setpoint

hysteresis

P 1 0

cold

s t a g e   O N

s t a g e   O F F

w a r m

Stage Cont Press. Transmitter (Condenser Fans)

The control setpoint is pre-
set by P04 as a pressure
value (this is the setpoint
for stage 1 at the same
time). There is no need for
an access code. The fol-
lowing stages switch in a
distance to the previous
stage (P05, P06, P07). The hysteresis
P10 is located symmetrical around the setpoints.

Forward (Stages on)
If the measured pressure value exceeds one of the setpoints
(P04 - P07) plus ½ P10 (hysteresis), the forward delay P20
will be started. After this timer is run down, the corresponding
stage will be activated and the timer starts again. Read at
P33 if a delay time is still running and when a stage will be
switched on or off.

Neutral zone
If the actual pressure value is located within the limits set by
P10 (hysteresis, located around all setpoints), then no stage
will be activated or de-activated.

Backrun (Stages will be switched off)
If the actual pressure value falls short of a setpoint - ½ P10,
the backrun delay P21 will be started. After this timer is run
down, the corresponding stage will be switched off, the timer
starts again, and so on.

hysteresis 

P 1 0

setpoint

cold

s t a g e   O N

s t a g e   O F F

w a r m

Summary of Contents for MSR 100 Series

Page 1: ...ge Compressors l Inputs for 2 wire Pressure Transmitters Pressostat and Temperature Sensors l Automatic Base Load Change Stage Sequence Change l Autoadaptive Trend Recognition l Analogue Output 0 10V...

Page 2: ...se order separately For usage with compressor compounds 2 wire pressure transmitter type DG 0 10 GSW with 4 20mA output signal For usage with condernser fans 2 wire pressure transmitter type DG 0 25 G...

Page 3: ...utes Reading the current operating mode Press and hold P longer than 3 seconds One of this 3 values occur on the display 106 Mode for compressor compounds 206 Mode for condenser fans 300 Mode for brin...

Page 4: ...value all stages will be switched OFF in 1 sec steps after P15 is run down alarm relay will be activated P15 X X X 88 Alarm time delay 0 0 0 0 60 min P16 X X X 70 Power stages of compressor resp fan 1...

Page 5: ...setpoint 1 0 0 0 0 59 min P38 X X X 88 OFF time hours of 2nd setpoint 1 0 0 0 0 23 h P39 X X X 88 OFF time minutes of 2nd setpoint 1 0 0 0 0 59 min P40 X X X 88 Adress of the unit in a network 78 78 7...

Page 6: ...ting From every state of the con troller 4 minutes after the last keypress the display switches back to the actual value Calibration of Transmitter and Actual Value A pressure transmitter delivers its...

Page 7: ...on Stage Controller for Brine Chillers The control setpoint is pre set by P04 as a tempera ture value this is the set point for stage 1 at the same time There is no need for an access code The follow...

Page 8: ...nd of the actual value and decides based on the captured data about the necessity of switching on off a machine A typical example of a conventional control is the following state Machines run the actu...

Page 9: ...signal Because this output is scalable it can be used both to forward an image of the actual value P01 or as proportional controller output P42 fixes the actual value the analogue output delivers 10V...

Page 10: ...m one transformer MSR 1100 only a double pole switch must be used to switched off the single positions If not the unit will be supplied by a half wave via the shielding andtheunitcontinuesworking depe...

Page 11: ...wer Hold key P until _ _ _ appears Let go key P Select 2 _ _ by key condenser fan mode Push key P once def appears default values are loaded Actual values appear ready for start up Basic Configuration...

Page 12: ...rward backrun Pressostat rear view with mounting frame 75 2 95 9 1 2 3 4 5 7 6 8 20 21 22 19 18 16 17 23 24 37 1 46 11 10 12 14 15 13 10 Multi Channel Controller F2 Mehrstufenregler ELREHA 15 A C D C...

Page 13: ...p alarm RS 485 N D O D O 37 36 35 30 29 Temperature Sensor Connection MSR 3100 23100 for chillers simplified picture 36 MSR 3100 38 37 RS 485 29 D O N D O 30 backrun forward Pressostat Dimensions MSR...

Page 14: ...K3 relay K4 alarm M M 14 9 10 12 11 13 15 29 N 24V DC f transmitter O K 1 D O 26 25 28 O K 2 30 MSR 5100 25100 with temperature sensors simplified pic 12 13 14 15 2 3 24 25 4 5 6 7 8 9 10 11 26 27 28...

Page 15: ...28 24 22 18 F1 DO NDO RS 485 relay 4 alarm F2 4 20mA 14 10 12 z 6 OK1 OK2 8 2 N 4 4 20mA N 16 relay 3 28 32 30 26 24 22 20 18 F1 18VDC RS 485 NDO DO 0 10V DC relay 4 alarm F2 10 14 12 6 8 2 4 d relay...

Page 16: ...lectromagnetic consistency IEC 1000 4 1 IEC 1000 4 2 IEC 1000 4 3 IEC 1000 4 4 IEC 1000 4 5 EN 55011 B EN 50081 part 1 and 2 EN 50082 part 1 and 2 EN 61010 part 1 EN 61010 1 A2 part 1 A1 This statemen...

Reviews: