background image

Page 10

Technical Manual MSR Universal Stage Controller

 Real time clock

The  MSR Controller contains a real time clock (without a date
function) which can be used for changing the control setpoint.
The timer has a data backup for about 10 days in case of power
failure.
The time of the day and the date can be set with parameters P45 thru
P47.
The time switch is de-activated if ON and OFF-time are identical.

 Operation Time Counter

Each relay output owns an individual operation time counter. This
counter measures and totalizes the time this output was activated.
The values can be read at "r01" thru "r04".
Because the display has 3 digits only, the stored value is "

displayed

value x 10".
After 9999 hours the counter will be reset to "0". A reset by the user
is not possible.

Networking of MSR controllers

All MSR-controllers can be networked via their
built-in RS-485-interface. This network can be
controlled by a host unit.
Normally this host is a PC with a qualified software
which allows remote control of units and recording
of all parameters.

2 4 V   A C

Inportant
with one
transformer 
only :

Switch off 
by double 
pole switch !

P E

N    PE

D O       N D O

T

N    PE

D O       N D O

shielding

T

T

N    PE

D O       N D O

T

N    PE

D O       N D O

Because all units are connected parallel at the data
cable (party-line), every unit has its own network
address (P40) to ensure a specific communication.

The communication speed is fixed by P41  (Default
value 9600 Baud).

If multiple, networked controller units are supplied
from one transformer (MSR 1100 only), a double
pole switch must be used to switched off the single
positions.
If not, the unit will be supplied by a half-wave via the
shielding, and the unit continues working (depending
on the secondary voltage of the transformer).

 INSTALLATION

Before applying voltage to the controller:
Make sure that all wiring has been made in
accordance with the wiring diagram in this manual.
Please check if the supply voltage corresponds to
the value printed on the unit's type label.

• Important for the installation of the MSR 1100:

Don't connect the secondary coil of the transformer to PE!

• Use 2-wire pressure transmitters only, 3-wire transmitters can

only be used with an external power supply.

• Important ! Please note the starting-currents and current

timing of your load to prevent damages of the relay
contacts.

• Sensor leads should be shielded cable with one end of the

shielding connected to ground. This avoids irregular
switching caused by electro-magnetic interference.

• The wire gauge of the sensor cables is not critical, if it

should be lenghtened, 0,5 sqmm are adequate.

• Mounting the controller close to power relays is

unfavourable in case of the electro-magnetic interference.

• Please note that TF-type temperature sensors are water-

proof but not pressure protected. To measure liquid media
please use dip-fittings.

• Important for the installation of the MSR 1100:

The external contacts for initiating the OK-input must be suitable
for 5VDC/1mA.

Attention !
Note polarity while 
connecting cables !

= sensor 
   common
   terminal

P E

T

N    PE   

DO   NDO

N    PE

T

DO   NDO

shielding

N    PE   

T

T

DO   NDO

N    PE 

T

Connections
as short as
possible !

5 cm max.

(2.0 inch)

DO   NDO

Summary of Contents for MSR 100 Series

Page 1: ...ge Compressors l Inputs for 2 wire Pressure Transmitters Pressostat and Temperature Sensors l Automatic Base Load Change Stage Sequence Change l Autoadaptive Trend Recognition l Analogue Output 0 10V...

Page 2: ...se order separately For usage with compressor compounds 2 wire pressure transmitter type DG 0 10 GSW with 4 20mA output signal For usage with condernser fans 2 wire pressure transmitter type DG 0 25 G...

Page 3: ...utes Reading the current operating mode Press and hold P longer than 3 seconds One of this 3 values occur on the display 106 Mode for compressor compounds 206 Mode for condenser fans 300 Mode for brin...

Page 4: ...value all stages will be switched OFF in 1 sec steps after P15 is run down alarm relay will be activated P15 X X X 88 Alarm time delay 0 0 0 0 60 min P16 X X X 70 Power stages of compressor resp fan 1...

Page 5: ...setpoint 1 0 0 0 0 59 min P38 X X X 88 OFF time hours of 2nd setpoint 1 0 0 0 0 23 h P39 X X X 88 OFF time minutes of 2nd setpoint 1 0 0 0 0 59 min P40 X X X 88 Adress of the unit in a network 78 78 7...

Page 6: ...ting From every state of the con troller 4 minutes after the last keypress the display switches back to the actual value Calibration of Transmitter and Actual Value A pressure transmitter delivers its...

Page 7: ...on Stage Controller for Brine Chillers The control setpoint is pre set by P04 as a tempera ture value this is the set point for stage 1 at the same time There is no need for an access code The follow...

Page 8: ...nd of the actual value and decides based on the captured data about the necessity of switching on off a machine A typical example of a conventional control is the following state Machines run the actu...

Page 9: ...signal Because this output is scalable it can be used both to forward an image of the actual value P01 or as proportional controller output P42 fixes the actual value the analogue output delivers 10V...

Page 10: ...m one transformer MSR 1100 only a double pole switch must be used to switched off the single positions If not the unit will be supplied by a half wave via the shielding andtheunitcontinuesworking depe...

Page 11: ...wer Hold key P until _ _ _ appears Let go key P Select 2 _ _ by key condenser fan mode Push key P once def appears default values are loaded Actual values appear ready for start up Basic Configuration...

Page 12: ...rward backrun Pressostat rear view with mounting frame 75 2 95 9 1 2 3 4 5 7 6 8 20 21 22 19 18 16 17 23 24 37 1 46 11 10 12 14 15 13 10 Multi Channel Controller F2 Mehrstufenregler ELREHA 15 A C D C...

Page 13: ...p alarm RS 485 N D O D O 37 36 35 30 29 Temperature Sensor Connection MSR 3100 23100 for chillers simplified picture 36 MSR 3100 38 37 RS 485 29 D O N D O 30 backrun forward Pressostat Dimensions MSR...

Page 14: ...K3 relay K4 alarm M M 14 9 10 12 11 13 15 29 N 24V DC f transmitter O K 1 D O 26 25 28 O K 2 30 MSR 5100 25100 with temperature sensors simplified pic 12 13 14 15 2 3 24 25 4 5 6 7 8 9 10 11 26 27 28...

Page 15: ...28 24 22 18 F1 DO NDO RS 485 relay 4 alarm F2 4 20mA 14 10 12 z 6 OK1 OK2 8 2 N 4 4 20mA N 16 relay 3 28 32 30 26 24 22 20 18 F1 18VDC RS 485 NDO DO 0 10V DC relay 4 alarm F2 10 14 12 6 8 2 4 d relay...

Page 16: ...lectromagnetic consistency IEC 1000 4 1 IEC 1000 4 2 IEC 1000 4 3 IEC 1000 4 4 IEC 1000 4 5 EN 55011 B EN 50081 part 1 and 2 EN 50082 part 1 and 2 EN 61010 part 1 EN 61010 1 A2 part 1 A1 This statemen...

Reviews: