Technical Manual MSR Universal Stage Controller

  Technical Data

Supply Voltage ................... see type survey
Power Consumption ........... appr. 3,5 VA
Output Relays ..................... 4 x potential free
Contact Rating .................... 8A cos phi=1, 3A ind. / 250V AC
Operating-/Storage-
temperature ........................ -10...+55°C / -30...+70°C
Ambient Humidity ............... max. 85% r.H., not condensing
Signal Inputs ....................... 4...20mA, Pressostat,

2x TF 201 / TF 501, selectable

Supply Voltage for
2-wire pressure transm. ..... appr. 24 VDC unreg., 23mA max

MSR 1100 ......... appr. 12 VDC reg., 21mA max.

Display ................................ LED 7-segm., red, char. height 13mm

19"-module: char. height 10mm

Resolution ........................... 0,1
Control-/Display Range ...... see parameter listing
Data storage parameters ... typ. 10 years
Real Time Clock ................. clock backup appr. 10 days
Indicator LED's ................... 3 mm, red
Control Inputs (Optocpl.) .... like mains voltage, 3mA max.

(MSR 1100: potential free contact)

Analogue Output ................. 0-10 V DC, max. 3 mA
Resolution Analogue Outp. . 8 bit between limit parameters
Data Interface .....................

E-Link (RS-485)

Electrical Connection ......... Screw terminals 2,5mm

19"-module: DIN41612"F"-connector

Housing, Protection

MSR 1100 ............... 77 x 35 mm, IP 54 from front
MSR 3100/23100 .... DIN-rail housing, IP 30
MSR 5100/25100 .... 96 x 48 mm, IP 54 from front
MSR 19100/29100 .. 19", 8 TE

Further informations you will find on the parameter listing.

 Type Overview

MSR 1100 ........... panel mounting, 12-24V AC/DC
MSR 3100 ........... for 35mm DIN-rail 230V~, 50-60 Hz
MSR 3100 ST ...... like above, but pluggable terminals
MSR 5100 ........... panel mounting, 230V~, 50-60 Hz
MSR 19100 ......... 19"-module, 8TE, 230V~, 50-60 Hz
MSR 23100 ......... for 35mm DIN-rail 110V~, 60 Hz
MSR 25100 ......... panel mounting, 110V~, 60 Hz

MSR 29100 ......... 19"-module, 8TE, 110V~, 60 Hz

  Accessories (please order separately)

For usage with compressor compounds
• 2-wire pressure transmitter type DG 0/10 GSW with 4-20mA

output signal

For usage with condernser fans
• 2-wire pressure transmitter type DG 0/25 GSW with 4-20mA

output signal

For usage with brine-chillers
• 2 x temperature sensor TF 201 (PTC) or TF 501 (Pt 1000)

For MSR 1100 only:
- Transformer  107-1300-0052

(220/12V / 5VA) or similar

For 19"-module:
- 19"-subrack or panel housing

 Contents

Page

Operating / Operating Elements ....................................... 3
Authorized Manipulating / Unlock Keys ............................ 3
Mode-(status) Display ....................................................... 3
Parameter Listing .............................................................. 4-5
Functional Description ...................................................... 6
Trend Analysis ................................................................... 8
Installation ......................................................................... 9
Start Up .............................................................................. 10
Physical Dimensions / Connections ................................. 11

Manufacturer:

25109 Terminal Drive South

St. Petersburg, Florida 33712

phone (+1) 727-327-6236

e-mail: [email protected]

Elektronische
Regelungen GmbH

D-68766 Hockenheim, Germany

Schwetzinger Str. 103

Telefon  (+49) (0) 62 05 / 2009-0

internetwww.elreha.de
e-mail [email protected]

Controls

 Safety Instructions

Please read before Start-up

• Electrical Installation and Start Up must be done from

authorized personnel.

• This product may only be used for the purposes listed on

page 1.

• Please note the local safety instructions !

• Before using the controller, please check if the unit fits

the application.

• Before applying voltage to the controller:

Make sure that all wiring has been made in accordance with
the wiring diagram in this manual.
Check, if the supply voltage corresponds to the value printed
on the unit's type label.

• Please pay attention to the specified Temperature-/Humidity

Limits. Outside these limits malfunctions may occur.

• Never operate unit without housing.

• Please note maximum load of relay contacts

(see technical data).

• Important ! Please note the starting-currents and current

timing of the load.

Summary of Contents for MSR 100 Series

Page 1: ...ge Compressors l Inputs for 2 wire Pressure Transmitters Pressostat and Temperature Sensors l Automatic Base Load Change Stage Sequence Change l Autoadaptive Trend Recognition l Analogue Output 0 10V...

Page 2: ...se order separately For usage with compressor compounds 2 wire pressure transmitter type DG 0 10 GSW with 4 20mA output signal For usage with condernser fans 2 wire pressure transmitter type DG 0 25 G...

Page 3: ...utes Reading the current operating mode Press and hold P longer than 3 seconds One of this 3 values occur on the display 106 Mode for compressor compounds 206 Mode for condenser fans 300 Mode for brin...

Page 4: ...value all stages will be switched OFF in 1 sec steps after P15 is run down alarm relay will be activated P15 X X X 88 Alarm time delay 0 0 0 0 60 min P16 X X X 70 Power stages of compressor resp fan 1...

Page 5: ...setpoint 1 0 0 0 0 59 min P38 X X X 88 OFF time hours of 2nd setpoint 1 0 0 0 0 23 h P39 X X X 88 OFF time minutes of 2nd setpoint 1 0 0 0 0 59 min P40 X X X 88 Adress of the unit in a network 78 78 7...

Page 6: ...ting From every state of the con troller 4 minutes after the last keypress the display switches back to the actual value Calibration of Transmitter and Actual Value A pressure transmitter delivers its...

Page 7: ...on Stage Controller for Brine Chillers The control setpoint is pre set by P04 as a tempera ture value this is the set point for stage 1 at the same time There is no need for an access code The follow...

Page 8: ...nd of the actual value and decides based on the captured data about the necessity of switching on off a machine A typical example of a conventional control is the following state Machines run the actu...

Page 9: ...signal Because this output is scalable it can be used both to forward an image of the actual value P01 or as proportional controller output P42 fixes the actual value the analogue output delivers 10V...

Page 10: ...m one transformer MSR 1100 only a double pole switch must be used to switched off the single positions If not the unit will be supplied by a half wave via the shielding andtheunitcontinuesworking depe...

Page 11: ...wer Hold key P until _ _ _ appears Let go key P Select 2 _ _ by key condenser fan mode Push key P once def appears default values are loaded Actual values appear ready for start up Basic Configuration...

Page 12: ...rward backrun Pressostat rear view with mounting frame 75 2 95 9 1 2 3 4 5 7 6 8 20 21 22 19 18 16 17 23 24 37 1 46 11 10 12 14 15 13 10 Multi Channel Controller F2 Mehrstufenregler ELREHA 15 A C D C...

Page 13: ...p alarm RS 485 N D O D O 37 36 35 30 29 Temperature Sensor Connection MSR 3100 23100 for chillers simplified picture 36 MSR 3100 38 37 RS 485 29 D O N D O 30 backrun forward Pressostat Dimensions MSR...

Page 14: ...K3 relay K4 alarm M M 14 9 10 12 11 13 15 29 N 24V DC f transmitter O K 1 D O 26 25 28 O K 2 30 MSR 5100 25100 with temperature sensors simplified pic 12 13 14 15 2 3 24 25 4 5 6 7 8 9 10 11 26 27 28...

Page 15: ...28 24 22 18 F1 DO NDO RS 485 relay 4 alarm F2 4 20mA 14 10 12 z 6 OK1 OK2 8 2 N 4 4 20mA N 16 relay 3 28 32 30 26 24 22 20 18 F1 18VDC RS 485 NDO DO 0 10V DC relay 4 alarm F2 10 14 12 6 8 2 4 d relay...

Page 16: ...lectromagnetic consistency IEC 1000 4 1 IEC 1000 4 2 IEC 1000 4 3 IEC 1000 4 4 IEC 1000 4 5 EN 55011 B EN 50081 part 1 and 2 EN 50082 part 1 and 2 EN 61010 part 1 EN 61010 1 A2 part 1 A1 This statemen...

Reviews: