Service menu
Press the Customer Service button in the System setup
(→ chapter 4)
A password must then be entered to access the Service
menu.
Login
Many sensitive settings can have additional password
protection assigned to them in the Service menu. So that
it is not necessary to enter the password every time, it is
also possible to login "globally". To do this, it is only
necessary to press the "Login" button and then enter the global password.
7.1
Setup SPG20
All parameters concerning the SPG20 control module, can be changed in this list.
The circled parameter can be changed by pressing within the frame.
Parameter
Valid Values
Description
Calculation by SBR South
Tyrol option
on/off
Activate the control button to activate the South
Tyrol
consulting group's spray calculation.
This also relates to the type of input in the
spray programmes (→ chapter 3.2.2).
With fan cover
on/off
Two additional buttons are made available
in the main window for controlling the fan
cover with this setting. (Only possible with a
maximum of six nozzle rings).
Control time for pressure
control with speed limit
2 ÷ 20
Standard=5
[seconds]
This is where the length of time is entered for
which the computer will wait before starting to
reduce the pressure if the vehicle drops below
the input speed. (Only when the “minimum
speed” function is active → chapter 6.8)
Spray programme allowed
on/off
This control button has to be activated to allow
working with the help of the spray programmes.
Otherwise you can only work with manual or
automatic pressure control.
Save spray programmes
into flash memory?
on/off
If the sprayer control is used without a PC
programme (without releasing memory while
transferring data to the PC), the function must
be deactivated.
Multi-row version?
on/off
Must be activated in the case of multi-row
sprayers, as the application rate is
calculated differently with multi-rows.
Tunnel type (only with multi-
row)
on/off
In the case of tunnel sprayers (only if the
“multi-row version” is activated)
Pressure sensor max value
20 ÷ 60
(standard=40)
[bar]
The pressure at which the pressure sensor
provides the maximum current of 20mA.
Example:
Sensor: 4…20mA
≙
0...40bar → i.e. 40 bar
Fig. 36: Service menu