M1XSLC Installation Manual - 

LUTRON HOMEWORKS QS

 

Page 10

LUTRON HOMEWORKS QS

Lutron's TouchPro Wireless HVAC Thermostats are compatible with the Lutron Homeworks QS system.  The M1XSLU can 

interface with up to sixteen (16) of these thermostats, but special steps are needed due to the architecture of the equipment.   

1. Only Device IDs below 100 (2 digits) may be used for HVAC Thermostats.  2. The M1 has to initialize the M1XSLU with the 

Device ID (2 digit) of each HVAC Thermostat.  This is done by having the M1 send a special text string command 

<TS 

to the 

M1XSLU followed by a two (2) digit Device ID for each Thermostat.  The M1XSLU takes this and maps each to an M1 Thermostat 

location (1-16).  

The Lutron Homeworks QS Designer PC Software is required to setup the Lutron HVAC Thermostats and to assign each one a 

unique Device ID.  This software also provides a means to view ALL of the installed Device IDs.   The ElkRP PC software and 

Automation Rules programming is required to setup the M1XSLU and to create the text strings and rules for sending the Device 

IDs of the HVAC Thermostats.  Please follow each of the steps below.

NOTE: On power-up the M1XSLU performs a Discovery Mode (~ 2 1/4 minutes) to obtain the status for all lighting devices.  

When complete the M1XSLU will send text string <DE^M  (Discovery End).  In order to set up Thermostats two (2) ElkRP 

rules must be written.  The first is used to detect the <DE^M string and start a delay timer.  The next will execute when the 

delay timer expires and send text string <TS along with the Device IDs of each Thermostat.  See Steps 4.4 &  4.5

 

5.1

  Use the Lutron Homeworks QS Designer  PC software to setup the Homeworks QS System.  THIS IS A REQUIREMENT!   

During setup each device (Controller, Dimmer, Keypad, HVAC Thermostat) will be assigned a unique Device ID.  Refer to the 

Reports > Integration menu to view a listing of these device ids, including the HVAC Thermostats and use this information to 

fill-in the ID of each Lutron HVAC Themostat in the spaces below. 

 

HVAC Thermostats may only reside at IDs below 100.

 

1st Thermostat ID = __ __   2nd= __ __   3rd= __ __   4th= __ __   5th= __ __   6th= __ __   7th= __ __   8th= __ __

 

9th Thermostat ID = __ __   10th= __ __   11th= __ __   12th= __ __   13th= __ __   14th= __ __   15th= __ __   16th= __ __

5.2

  Launch ElkRP Software and open or create an account for this job.  If using a previously programmed account, make sure the 

ElkRP file and M1 Panel are synchronized with the same data.  If in doubt, connect to M1 and select Receive All to bring all the 

info from M1 into your ElkRP account file. 

5.3

 Click 

> Automation > Thermostats

 and program a descriptive name for each Thermostat that is being integrated.  A NAME IS 

MANDATORY.  M1 will ignore (not display) any Thermostat location that does not have a name.

4.4 

Click 

> Automation > Texts

 and program 2 new text strings.  As mentioned, the texts strings will be used in Automation Rules 

to: 1)Detect the end of Discovery Mode and 2)Send the Thermostat Device IDs to the M1XSLU. 

 Click 

New

 to create the 1st text string.   Enter the first text string as:  

<DE^M   

then click OK.

 Click 

New

 to create the 2nd text string.   Start this string with 

<TS 

and follow with the Device ID of the first thermostat (refer 

to step 4.1).  In the case of multiple thermostats separate each Device ID with a comma ",".  End the string with a 

^M

.  An 

example of a text string for 3 thermostats numbered 19,30, & 56 would be 

<TS19,30,56^M   

Click OK when done.   

NOTE: Each ID entry after <TS MUST BE TWO (2) DIGITS.  e.g 01 to 09, 10, etc.  1 thru 9 will not work.

Adding Lutron TouchPro Wireless Thermostats to M1

Summary of Contents for ELK-M1XSLC

Page 1: ...a Line HOMEWORKS QS INSTRUCTIONS Specifications are Subject to Change without notice NOTICE Drawings illustrations diagrams part numbers etc are provid ed as reference only and are based on equipment...

Page 2: ...less it was setup and programmed by the QS Designer software Lutron Certification training may be required to obtain this sofware This is restriction imposed by Lutron not Elk Integration Capacity Eac...

Page 3: ...pplied P1216 plug in AC to DC power supply Connect power supply to barrel connector on IP232 2 8 If all wired connections are complete and secure it is now OK to apply power to the M1 Control which al...

Page 4: ...re available h Choosing an update 1 Bootware Update This step may be skipped unless specifically required by the firmware update Please refer to the release notes for the current update Use the scroll...

Page 5: ...icult for the Configuration Utility to discover it Should this occur the most likely problems could be 1 The client s router is not assigning DHCP addresses 2 The client s router has reached its limit...

Page 6: ...168 1 157 for the Lutron Homeworks QS Processor A In the Outgoing Connection box click Add New to start the rule wizard B Enter the IP Address of the Lutron Homeworks QS Processor We highly recommend...

Page 7: ...known to be used by Lutron at the time this manual was printed Below are the Login prompts and the replies shown in BOLD For Prompt for User Name enter login For Prompt for Password enter password Fo...

Page 8: ...in doubt connect to M1 and select Receive All to bring all the info from M1 into your ElkRP account file 4 5 Select the first Homeworks QS Device ID and match it to its M1 Light Device number location...

Page 9: ...or ramp Fade Rate 1 Light s will fade ramp on over a 2 seconds Fade Rate 2 Light s will fade ramp on over a 4 seconds Fade Rate 3 Light s will fade ramp on over a 8 seconds Fade Rate 4 Light s will f...

Page 10: ...IS A REQUIREMENT During setup each device Controller Dimmer Keypad HVAC Thermostat will be assigned a unique Device ID Refer to the Reports Integration menu to view a listing of these device ids incl...

Page 11: ...BE MIXED combined with other HVAC Thermostat technologies or brands on the same job I E Do not mix hardwired units such as RCS RS485 Leviton RS232 or Aprilaire RS485 on the same M1 panel with Lutron...

Page 12: ...ostats E G Main Hallway Tstat 1 5 13 Click Set heating desired temperature to 5 14 In the value box scroll to set the temperature value Set the F or C box to your preference Then click OK The screen s...

Page 13: ...below M1 rules can be triggered in response to button presses on a wall or tabletop keypad providing a method to control outputs tasks etc when a button is pressed on the Homeworks QS device This is...

Page 14: ...d with M1 It is used to send the Device IDs of each thermostat to the M1XSLU This allows the M1XSLU 1 To know the ID of each existing Lutron thermostat 2 To query the status of each and to map the dat...

Reviews: