Elk Products ELK-M1XSP Installation Manual Download Page 14

M1XSP Installation Manual

Page 14

UPB 

is a PLC or Powerline Communications lighting technology.  There are 2 methods for interfacing UPB to M1.  First is an

ELK-M1XSP connected to a UPB PIM 'S" (RS232 Serial Program Interface Module).   Second is a new product called the
ELKM1PCSPIM (or PCSPIM 'E').  This product looks like an ordinary PIM but actually contains both a PIM and M1XSP processor
module.  It connects directly to the M1 Data Bus and eliminates the RS232 cord/connection.  NOTE: The M1PCSPIM is internally
fixed to M1 Bus Address #7, meaning that no other M1XSP's on the bus may be set to that address.  Regardless of the type of
connection, M1 supports up to 192 UPB individual addresses (dimmers, switches) and 64 UPB Links (scenes).

Integration is accomplished by "mapping" the UPB addresses and operation to M1 Lighting device entities.  UPB device
addresses 1-192 map to M1 Lighting devices 1-192.  UPB Links 1-64 map to M1 Lighting devices 193-256.  NOTE: Links
require M1XSP firmware version 1.0.14 or higher.  The chart on the next page shows the M1 Light devices and UPB mappinig.

Components required for UPB integration:

-

ELK-M1 or ELK-M1EZ8 Controller and the ElkRP Programming Software.

-

ELK-M1XSP Serial Port Expander.  Firmware updating may be required and may be downloaded from the ELK Web site.

-

UPB PIM (Programming Interface Module)   { or ELKM1PCSPIM which is internally fixed to M1 Bus Address #7}

-

One or more UPB Lighting devices plus the UPB PC Programming Software called "UPStart."

Setting up to communicate with UPB   { Skip steps 1 - 4 if you are using the new ELKM1PCSPIM }

1.

Install the ELK-M1XSP per the instructions on page 3.  Be sure to enroll the device into the M1.

2.

Connect the female end of the supplied 9-pin serial cable to the M1XSP and the male end to the UPB PIM Module.

3.

Set the 

MODE

 Jumpers on the M1XSP as follows: 

S4*="1" (UP), S5="1" (UP), S6="1" (UP), S7="0" (DN), S8="1" (UP).

NOTE: Some units do not have jumper S4.

4.

Set the M1XSP Jumper 

JP3="232"

.   Set 

JP5

 to 

ON

.  The position of BAUD jumpers S1,S2,S3 does not matter.

5.

Power up all the devices.

6.

Using the ElkRP software, open the "Globals" folder.  Then go to the "G29-G42 Special" tab and program the same unique
UPB NETWORK ID into the M1 that is stored in the UPB switches.

DO NOT USE NETWORK ID 0 OR 255 AS THESE ID HAVE SPECIAL PURPOSE RESERVED BY UPB.

7.

In the ElkRP software open the Automation > Lighting folder and program the M1 Lighting devices.  Only the devices
specifically for UPB use will need to be programmed.  For UPB individual addresses program M1 Lighting devices:  

1-192

as: Format=Serial Expander, Type= Dimmer (or "On/Off Switch" if the device isn't dimmable)

.   For UPB link addresses

program M1 Lighting devices: 

193-256 as: Format= Serial Expander,  Type=On/Off Switch.

When an M1 Light device is activated from a rule or from the M1 Keypad "Automation" menu, the corresponding device com-
mand will be sent onto the powerline network to the UPB Devices.

Programming the UPB devices:

The UPB UPStart Software must be used to program each UPB module with an address, a network ID, and any other options.

IMPORTANT: 

The UPB NETWORK ID programmed into the UPB switches MUST MATCH the UPB NETWORK ID programming

into the ElkRP software.  [ElkRP Globals folder > G29-G42 Special tab.  DO NOT USE NETWORK ID 0 or Network ID 255.

UPB Device Status:

In order to receive "Load Status" changes from the UPB devices, make sure to program their option bit "Transmit Changes".

LIMITATIONS  - CURRENT STATUS FROM UPB MODULES

Status reports resulting from manual rocker (pushbutton) changes.  - UPB devices may be optionally programmed to
broadcast (report) their individual status whenever a manual change occurs via the rocker (pushbutton) switch.  This
option requires UPStart PC Software and each device must be individually programmed.  Go to tab labeled "Rocker
Switch".  On this tab place a checkmark in the box option labeled "Report light level after rocker switch is pressed."

Status reports resulting from UPB LINK commands. - UPB devices DO NOT and CANNOT be programmed to broad-
cast (report) their status when changed by a LINK command.  Because a LINK can affect anywhere from 1 to 255
devices simultaneously, the communications protocol does not permit status reports because the entire performance of
the UPB network could be adversly affected.  For this reason, the status displayed by M1 Controller may not always
match the true status of UPB devices when devices are controlled by a Link command.  This is a UPB protocol issue
and there is nothing (NO WORKAROUND) that Elk can do to resolve this issue.

PC based software packages with access to lots of memory are able to memorize which UPB switches belong to each
LINK along with their programmed (expected) response to each LINK.  From this they are able to either anticipate the
expected status OR poll only each affected device in order to obtain their status report.  But even this is not practical
when large numbers of devices are involved in a LINK.  Simply put, it can take up to 5 minutes to poll all 255 potential
UPB devices, during which network traffic and device communications would be totally swamped and messages lost.

UPB - (Individual Lighting Loads and Links)

Summary of Contents for ELK-M1XSP

Page 1: ...the capabilities or data definitions to permit additional integration beyond what is currently available In addition Partner Mfgs may at their option add modify or discontinued features or support wit...

Page 2: ...ettings via DIP Switches Jumper Options and LED Diagnostic indicator On Board EOL Bus Termination Jumper Flash Memory for Firmware Updating SPECIFICATIONS Maximum of Expandable Ports Units 7 with M1G...

Page 3: ...HAI Thermostats numbered 1 thru 4 Data bus address 2 for HAI Thermostats numbered 5 to 8 Data bus address 3 for HAI Thermostats numbered 9 to 12 Data bus address 4 for HAI Thermostats numbered 13 to 1...

Page 4: ...AI OnQ ALC UPB Centralite EDT Dynalite LutronRA W800RF32 etc 10 x x Field Installable Firmware Uplink AnyNet and AES Intellinet Radio 20 x x Field Installable Firmware Vizia RZCOP ZWave interface Down...

Page 5: ...Aprilaire baud rate is preset internally 4 Plug the Aprilaire supplied 6 ft RJ to DB9 Cable between the 8811 Protocol Adapter and the ELK M1XSP DO NOT USE THE ELK WO37A CABLE 5 Power up the Aprilaire...

Page 6: ...unit The White Yellow wire is optional It may be used to supply 12VDC from the M1XSP to the Thermostat in lieu of the HVAC power Consult the RCS manual for details Plug the other end of the ELK WO37A...

Page 7: ...preset internally 4 Using a 3 conductor cable and the diagram below connect the GND D and D wires from the RS 485 terminals on the RCS Thermostat Control unit to the RS 485 terminals on the M1XSP The...

Page 8: ...OmniStat 2 series the M1XSP must be firmware updated to version 70 0 2 or the latest 70 x x version 4 Set the M1XSP MODE jumpers to S5 1 S6 0 S7 1 S8 0 If the M1XSP has jumper S4 set it to 1 5 Set th...

Page 9: ...Data Bus Terminals VKP A B Neg ADDRESS Only Addresses 1 2 3 or 4 can be used with HAI Stats Address 1 shown Switch 1 on MODE For HAI set to 1010 1 0 Address 1 2 4 8 ELK M1XSP Interface 1 0 1 2 3 4 RS...

Page 10: ...assigned to Carrier System 2 Zone 2 Elk Thermostat 3 is assigned to Carrier System 1 Zone 3 Elk Thermostat 11 is assigned to Carrier System 2 Zone 3 Elk Thermostat 4 is assigned to Carrier System 1 Z...

Page 11: ...T FORGET TO ENROLL THE M1XSP INTO THE M1 9 Program and test at least one light device using the ELK RP Software and the following steps 9a Click on the Automation icon then on the Lighting icon 9b Cli...

Page 12: ...only support ALC 4 button scene switches wired and connected on ALC branch 1 Setting up the M1XSP and the M1 to communicate with OnQ ALC 1 Install the ELK M1XSP per the instructions on page 3 Be sure...

Page 13: ...4 F15 F16 G01 G02 G03 G04 G05 G06 G07 G08 G09 G10 G11 G12 G13 G14 G15 G16 H01 H02 H03 H04 H05 H06 H07 H08 H09 H10 H11 H12 H13 H14 H15 H16 ELK Light Device 129 130 131 132 133 134 135 136 137 138 139 1...

Page 14: ...individual addresses program M1 Lighting devices 1 192 as Format Serial Expander Type Dimmer or On Off Switch if the device isn t dimmable For UPB link addresses program M1 Lighting devices 193 256 a...

Page 15: ...1 192 PLC X 10 Ref I01 I02 I03 I04 I05 I06 I07 I08 I09 I10 I11 I12 I13 I14 I15 I16 J01 J02 J03 J04 J05 J06 J07 J08 J09 J10 J11 J12 J13 J14 J15 J16 K01 K02 K03 K04 K05 K06 K07 K08 K09 K10 K11 K12 K13 K...

Page 16: ...pander Type On Off Switch Load Status and or Limitations with Elegance and LiteJet The wallplate button press feature with LiteJet Elegance is not directly usable with M1 However by assigning a button...

Page 17: ...172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 PLC X 10 Ref I01 I02 I03 I04 I05 I06 I07 I08 I09 I10 I11 I12 I13 I14 I15 I16 J01 J02 J03 J04 J05 J06 J07 J08 J09 J10...

Page 18: ...nd 17 All On All Off respectively Program the name for light device 16 as All On Off Set the Format to Serial Expander and Type to On Off Switch Activating M1 lighting 16 On it will send Phantom 16 Ac...

Page 19: ...2 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 PLC X 10 Ref I01 I02 I03 I04 I05 I06 I07 I08 I09 I10 I11 I12 I13 I14 I15 I16 J...

Page 20: ...nked learned into the M1XSP starting at the first M1 Lighting device 001 A1 Using just the M1XSP there is no way to have devices start at a specific location INSTEON devices cannot be removed or re ar...

Page 21: ...e Right arrow key to access Menu 1 View Control Automation Fncts Press 2 followed by the right arrow key for the Lighting sub menu Advance to M1 Light 256 INSTEON LinkMode by entering 2 5 6 2 Turn ON...

Page 22: ...s an option to eliminate Groups and free up addresses 193 M1 to 254 P14 See note N2 below N1 With the M1XSP Jumper S5 0 factory setting the M1XSP supports a total of 192 individual INSTEON or X 10 Lig...

Page 23: ...H14 H15 H16 ELK Light Device 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 17...

Page 24: ...s c RS 232 Setup this may show up as HAI SETUP in some older remotes For helpful information about the ViziaRF configuration use the following link to the Leviton web site http www leviton com OA_HTML...

Page 25: ...be set as Backup B Optional Program a name to describe the location that this telephone number is reporting to C Do not program any numbers into the NUMBER TO DIAL location D Program the reporting for...

Page 26: ...ignals onto the AC powerline if equipped with a PSC05 PLC interface Please note that M1 rules can only be activated by ON or OFF commands from these devices There is no rule activation support for DIM...

Page 27: ...the AES Radio to be positioned far from the control 6 Construct a Serial Connection Cable from the M1XSP to the AES Radio Unit using the diagram below This cable requires a DB9F 9 Pin Female connecto...

Page 28: ...ING ELKRP SOFTWARE MAKE SURE TO SEND ALL OF THIS PROGRAMMING TO THE CONTROL 10 Test Test Test It is very important to test each of the reported events SUPERVISION The M1XSP is enrolled with M1 Control...

Page 29: ...esignated A and A1 Do the same for the data B White wire At the control splice the A1 and B1 wires to the A and B wires going to the next device Terminate the last wired device and the control JP3 ONL...

Page 30: ...keys to exit Installer Programming 1234567890123456789012345 1234567890123456789012345 1234567890123456789012345 1234567890123456789012345 1234567890123456789012345 1234567890123456789012345 12345678...

Page 31: ...M1XSP InstallationManual Page 31 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 32: ...engage a 120 Ohm resistor for terminating the M1 RS 485 Data Bus See M1 Data bus wiring instructions before use JP2 Used to engage a 120 Ohm resistor for terminating the Outbound External RS 485 Data...

Reviews: