Installation Manual
Page 12
Central Station Setup (optional)
The M1XEP supports Alarm over Internet Monitoring to Central Stations that support either the G.E. OH2000E or
DSC SurGard IP receivers.
Internet monitoring requires setup of the M1XEP as well as a corresponding telephone number in the Control:
Telephone number # 1 for CS1 in the M1XEP setup, Telephone number # 2 for CS2, etc.
1. Create a new telephone number in ElkRP. To do this, right click on the "Telephones" icon on the left side
of the screen. Choose "New Telephone". Enter the number of telephones to create and the first (starting)
telephone number ID and click OK.
2.
On the telephone number screen, enter a name and set the reporting format to 6 = IP. Dialing attempts
should be set to 1 to enable reporting.
3. In the "Report the following to this number" box, check all the events that should be reported to the Central
Station through the M1XEP.
4. Place a checkmark in the checkbox beside each area that will make reports to this Central Station.
5.
If the M1XEP will be the primary method of sending reports to the Central Station, select "0=Always report to
this number" from the Type dropdown box at the top of this screen. If the M1XEP will be used to send reports
to the Central Station as a backup method, select "1=Report to this number as a backup" from the Type
dropdown box.
6. Click the "Send to Control" button to store this information in the control. Click "Save" to save to database.