M1G Installation and Programming
Page 6
+SAUX
NEG
+VAUX
NEG
+VAUX
NEG
+VAUX
NEG
AC
NORMAL
ZONE 16
JP1
SW1
16.5 V
JUMPER TO START
WITH NO AC
POWER
TELCO SEIZED
AC
Z9
NEG
Z10
Z11
NEG
Z13
NEG
Z15
Z14
Z12
NEG
Z16
Z2
Z3
NEG
Z5
NEG
Z7
Z6
Z4
NEG
Z8
Aux12VDC Power Outputs
protected by 1.25A PTC NOTE:
Refer to Appendix F for the UL limitations on total continuous 'standby'
current drain from terSAUX, +VAUX, +VKP, and J16.
Replace Battery every 3-5 years.
Use ELK model #
ELK1280
(12V - 8 Ah) or
ELK12180
(12V - 18 Ah) or equivalent.
DIALER ACTIVE
SMOKE
2WIRE
STATUS
REVERSE
BAT LEADS
+
-
7
N.C.
N.O.
ZONE
2200
Ohm
EOL
8
N.C.
N.O.
ZONE
2200
Ohm
EOL
5
N.C.
N.O.
ZONE
2200
Ohm
EOL
6
N.C.
N.O.
ZONE
2200
Ohm
EOL
3
N.C.
N.O.
ZONE
2200
Ohm
EOL
4
N.C.
N.O.
ZONE
2200
Ohm
EOL
1
N.C.
N.O.
ZONE
2200
Ohm
EOL
2
N.C.
N.O.
ZONE
2200
Ohm
EOL
12 Volt
Sealed
Lead Acid
Control needs AC power to start. Momentarily shorting these two pads allows control to startup on battery only.
16.5VAC, 45VA UL Listed Class 2 Transformer -
ELK-TRG1640
DO NOT CONNECT TO A SWITCHED OUTLET
For Canada use cUL Listed Transformer -
ATC Frost # FPS-4016
18AWG Min.
NEG
Z1
15
N.C.
N.O.
ZONE
2200
Ohm
EOL
16
N.C.
N.O.
ZONE
2200
Ohm
EOL
13
N.C.
N.O.
ZONE
2200
Ohm
EOL
14
N.C.
N.O.
ZONE
2200
Ohm
EOL
11
N.C.
N.O.
ZONE
2200
Ohm
EOL
12
N.C.
N.O.
ZONE
2200
Ohm
EOL
9
N.C.
N.O.
ZONE
2200
Ohm
EOL
10
N.C.
N.O.
ZONE
2200
Ohm
EOL
Master Power Switch (SW1)
, disconnects AC and Battery power from control.
This unit provides Residential fire alarm service when installed according to ANSI/NFPA 72. Transmission
of the fire alarm signal to a fire alarm headquarters or central station shall be permitted only with the
approval of the authority having jurisdiction. The burglar alarm signal shall not be transmitted to a police
emergency number, equipment is to be installed in accordance with NFPA (985,55.1.P).
Recommended locations and wiring methods shall be in accordance with CSA C22.1, Canadian Electrical
Code, Part I, Safety Standard for Electrical Installations; CAN/ULC-S302, Installation and Classification of
Burglar Alarm Systems for Financial and Commercial Premises, Safes and Vaults; and CAN/ULC-S301,
Standard for Central and Monitoring Station Burglar Alarm Systems.
Reference NFPA70 (NEC) & Canadian Electrical Code.
All circuits are current limited except for Battery leads. Refer to Appendix F.
For Installation of Residential Fire Warning Systems reference CAN/ULC-S540 Standard.
Testing of this system should be performed regularly with the primary AC power de-energized. Control
panel specifications are subject to change without notice.
Lithium 3V "Clock" battery, Varta #CR2032 located in upper left corner behind cover. Battery has a life
expectancy of approx. 10 years. Replace ONLY with exact model available at most electronics and camera
retailers.
"CAUTION: Lithium Battery May Explode If Mistreated. Do Not Recharge, Disassemble, or
Dispose Of In Fire."
Dialer/Modem is idle. If ON, Dialer/Modem is in use (communicating).
1 blink with equal On and Off times is Normal. 2 fast blinks = Control running on
bootloader only. 4 fast blinks = Control is re-initializing it's EEPROM memory after
a firmware flash. 5 fast blinks = Memory/Operation overflow
Battery is connected correctly. If ON, check battery lead connections.
AC Voltage is present and power switch is turned ON. If OFF, check AC power.
Phone line is good and house phones are connected. If ON constantly, the phone
line may be bad. During remote mode this LED will be ON since the house phones
are then disconnected from the outside line & are being powered from control.
TELCO
SEIZED
DIALER
ACTIVE
OFF
OFF
LEDS
Indicators
Power
Regular 1
sec. Blink
ON
Battery
Reversed
OFF
Status
4-Wire Smoke Detector
2200
Ohm
EOL
To Zone Input
U.L. Listed EOL Supervision Relay
(
ESL #204
or Equivalent).
N.O. Alarm
Contacts
+
-
+
-
Sw12 VDC Output
protected by 1.1A PTC.
BATTERY
To Zone NEG
(Left Side Terminals)
Normal
State
Descriptions
Color Code for 2200
Ohm EOL Resistor
Part # ELK-ER2200
Color Code for 820
Ohm EOL Resistor
Part # ELK-ER820
NOTE: M1ZTS Temperature Sensors may only be connected to the first 16 zones.
Smoke Detector covers should be kept free
from dust and dirt by use of a dry or damp
(water) cloth as needed. When necessary,
clean the detector interior and/or replace the
optical chamber according to instructions
provided by the Smoke Detector Manufacturer.
+
2-Wire Smoke Detector
820
Ohm
EOL
+
-
NEG
Z16
Compatibility Identifier: M10001
Maximum Operating Voltage: 13.8 VDC
Max. wire resistance should not exceed 13 Ohms.
Use 18AWG Fire approved wire. Max. wire length = 1000 feet.
Do not
mix different models on same circuit as proper operation
may be impaired.
Name
System Sensor
Sentrol (GE)
Model
2W-B, 2WT-B, 1151, 2100, 2100T, 2151
429AT, 521BXT, 521B
Compatibility ID
A
S09A
Max #
20
20
Base
None
None
To configure Zone 16 as a 2-wire smoke zone, set Jumper JP1 to "2 WIRE SMOKE" and use 820
Ohm EOL resistor, part # ELK-ER820.
2-Wire Smoke Detector Compatibility
† †
M1G "Board only" non-alarm
current draw = 140mA ( .14 Amp )
Gray (8)
Red (2)
Brown (1 x 0)
Gold (quality)
Red (2)
Red (2)
Red (2 x 0)
Gold (quality)
Wiring & Hookup Diagram