SW 5250A•SW 3500A•SW 1750A
General Description
Operation Manual
1-3
The SmartWave sources are true DC as well as AC power supplies. Up to 312 VRMS
are available in AC or AC+DC modes. Multi-phase models can be switched to single or
three-phased operation via the front panel or the GPIB.
A wide frequency range of DC or 40 Hz to 5 kHz is available for a broad array of
applications. Utilizing the latest in AC switch mode technology, the SmartWave has
less than -60 dB of noise and ripple with total harmonic distortion (THD) of <0.5% to 500
Hz. A crest factor of 4.0 provides high peak-to-RMS current capability. An optional
power factor correction (PFC) of .99 is also available.
1.2
1.3
Input
Specifications
Input Power Ranges
: Factory configured 187 to 264 VRMS, 3
φ
L-L (3 wire),
or 342 to 457 VRMS, 3
φ
L-L (4 wire). A chassis ground is also required for safety.
Input Power Factor
: .6 with USA rectifier; .35 with INTL rectifier;
.99 with input PFC option.
Input Frequency Range
: 47 to 63 Hz (47 to 440 Hz for PFC input only)
Efficiency
: 70%, minimum, at full load.
Ride Through
: 3 msec, minimum; 10 msec, minimum, with PFC option.
Input Current
: Maximum currents are provided in Table 2–7 and Table 2–8.
Initial Turn-on Current Surge
: Limited to less than peak value listed in
Output Specifications: Normal Operation Mode
Calibration Interval
:
1 year.
Power Factor of Load
: 0 lagging to 0 leading.
AC or DC Output Voltage
: 0 to 156 VRMS L-N range 0; 0 to 312 VRMS L-N range 1.
Output Current Per Phase
: 13A at 135V in 156V range; 6.5A at 270V in 312V range
(1750 VA maximum).
Crest Factor
: 4.0 (peak output current to RMS output current).
Output Frequency
: DC, or 40 Hz to 5 kHz.
Output Power
: 1750 VA, maximum, per phase.
Summary of Contents for SmartWave SW1750A
Page 2: ... ...
Page 4: ...Committed to Quality Striving for Excellence ii ...
Page 5: ...This page intentionally left blank iii ...
Page 8: ......
Page 31: ...SW 5250A SW 3500A SW 1750A Installation Operation Manual 2 5 Figure 2 3 SmartWave Rear Panel ...
Page 66: ...Operation SW 5250A SW 3500A SW 1750A 3 22 Operation Manual Table 3 1 Sequence Execute Menu ...
Page 90: ......