Page 10
EA Elektro-Automatik GmbH
Helmholtzstr. 31-37 • 41747 Viersen
Germany
Fon: +49 2162 / 3785-0
Fax: +49 2162 / 16230
www.elektroautomatik.de
PSB 9000 3U Series
1.8.3
Specific technical data (EU models)
(1 Related to the nominal values, the accuracy defines the maximum deviation between an adjusted values and the true (actual) value.
Example: an 80 V model has min. 0.1% voltage accuracy, that is 80 mV. When adjusting the voltage to 5 V, the actual value is allowed to differ max. 80 mV, which
means it might be between 4.92 V and 5.08 V.
(2 RMS value: LF 0...300 kHz, PP value: HF 0...20MHz
(3 The display error adds to the error of the related actual value on the DC terminal
5 kW
Model EU
PSB 9060-120 PSB 9080-120 PSB 9200-70 PSB 9360-40 PSB 9500-30
AC supply
Voltage range (L-L), frequency
342...528 V AC, 45 - 66 Hz
Connection
2ph, PE
Fusing (internal)
2x T16 A
Leak current
< 3.5 mA
Phase current
max. 16 A
Efficiency of energy recovery
≤ 92.5%
≤ 92.5%
≤ 93.5%
≤ 93.5%
≤ 94.5%
DC terminal
Max. voltage U
Max
60 V
80 V
200 V
360 V
500 V
Max. current I
Max
120 A
120 A
70 A
40 A
30 A
Max. power P
Max
5000 W
5000 W
5000 W
5000 W
5000 W
Overvoltage protection range
0...66 V
0...88 V
0...220 V
0...396 V
0...550 V
Overcurrent protection range
0...132 A
0...132 A
0...77 A
0...44 A
0...33 A
Overpower protection range
0…5500 W
0…5500 W
0…5500 W
0…5500 W
0…5500 W
Temperature coefficient for set
values Δ/K
Voltage / current: 100 ppm
Capacitance (approx.)
7990 μF
7990 μF
2520 μF
390 μF
180 μF
Voltage regulation (general)
Adjustment range
0...61.2 V
0...81.6 V
0...204 V
0...367.2 V
0...510 V
Accuracy
(1
(at 23 ± 5°C)
< 0.1% U
Max
< 0.1% U
Max
< 0.1% U
Max
< 0.1% U
Max
< 0.1% U
Max
Line regulation at ±10% ΔU
AC
< 0.02% U
Max
< 0.02% U
Max
< 0.02% U
Max
< 0.02% U
Max
< 0.02% U
Max
Display: Resolution
See section
„1.9.6.4. Resolution of the displayed values“
Display: Accuracy
(3
≤ 0.2% U
Max
≤ 0.2% U
Max
≤ 0.2% U
Max
≤ 0.2% U
Max
≤ 0.2% U
Max
Remote sensing compensation
Max. 5% U
Max
Max. 5% U
Max
Max. 5% U
Max
Max. 5% U
Max
Max. 5% U
Max
Voltage regulation (power supply)
Load regulation at 0...100% ΔI
OUT
< 0.05% U
Max
< 0.05% U
Max
< 0.05% U
Max
< 0.05% U
Max
< 0.05% U
Max
Rise time 10...90%
ΔU
OUT
Max. 30 ms
Max. 30 ms
Max. 30 ms
Max. 30 ms
Max. 30 ms
Transient time after ΔI
OUT
< 1.5 ms
< 1.5 ms
< 1.5 ms
< 1.5 ms
< 1.5 ms
Ripple
(2
< 200 mV
PP
< 16 mV
RMS
< 200 mV
PP
< 16 mV
RMS
< 300 mV
PP
< 40 mV
RMS
< 320 mV
PP
< 55 mV
RMS
< 350 mV
PP
< 70 mV
RMS
Voltage regulation (el. load)
Load regulation at 0...100% ΔU
< 0.05% U
Max
< 0.05% U
Max
< 0.05% U
Max
< 0.05% U
Max
< 0.05% U
Max
Current regulation (general)
Adjustment range
0...122.4 A
0...122.4 A
0...71.4 A
0...40.8 A
0...30.6 A
Accuracy
(1
(at 23 ± 5°C)
< 0.2% I
Max
< 0.2% I
Max
< 0.2% I
Max
< 0.2% I
Max
< 0.2% I
Max
Line regulation at ±10% ΔU
AC
< 0.05% I
Max
< 0.05% I
Max
< 0.05% I
Max
< 0.05% I
Max
< 0.05% I
Max
Display: Resolution
See section
„1.9.6.4. Resolution of the displayed values“
Display: Accuracy
(3
≤ 0.2% I
Max
≤ 0.2% I
Max
≤ 0.2% I
Max
≤ 0.2% I
Max
≤ 0.2% I
Max
Current regulation (power supply)
Load regulation at 0...100% ΔU
OUT
< 0.15% I
Max
< 0.15% I
Max
< 0.15% I
Max
< 0.15% I
Max
< 0.15% I
Max
Ripple
(2
< 80 mA
RMS
< 80 mA
RMS
< 22 mA
RMS
< 18 mA
RMS
< 16 mA
RMS
Current regulation (el. load)
Load regulation at 0...100% ΔU
IN
< 0.15% I
Max
< 0.15% I
Max
< 0.15% I
Max
< 0.15% I
Max
< 0.15% I
Max
Ripple
(2
< 80 mA
RMS
< 80 mA
RMS
< 22 mA
RMS
< 18 mA
RMS
< 16 mA
RMS