A: Protocol Data Points for EIG Meters
Doc# E204701 A-5
Electro
Industries/GaugeTech
™
Powered by Innovation™
Point
Name
BACnet
Object
Type
BACnet
Object
ID
N2
Data
Type
N2
Point
Address
EIP
Tag
Name
DF1
Address
Lon
Name
Lon
SNVT
VAR
Ͳ
hours
Net
AI
34
AI
34
S32_XXX[6]
F11:6
nvoVARh_Net_XXX
SNVT_count_inc_f
VAR
Ͳ
hours
Total
AI
35
AI
35
S32_XXX[7]
F11:7
nvoVARh_Tot_XXX
SNVT_count_inc_f
Amps
A
Avg
AI
36
AI
36
Flt_XXX[27]
F10:27
nvoAmpA_Avg_XXX
SNVT_count_inc_f
Amps
B
Avg
AI
37
AI
37
Flt_XXX[28]
F10:28
nvoAmpB_Avg_XXX
SNVT_count_inc_f
Amps
C
Avg
AI
38
AI
38
Flt_XXX[29]
F10:29
nvoAmpC_Avg_XXX
SNVT_count_inc_f
Positive
Watts
3
Ͳ
Ph
Avg
AI
39
AI
39
Flt_XXX[30]
F10:30
nvoPsWat3PAv_XXX
SNVT_count_inc_f
Positive
VARs
3
Ͳ
Ph
Avg
AI
40
AI
40
Flt_XXX[31]
F10:31
nvoPsVAR3PAv_XXX
SNVT_count_inc_f
Negative
Watts
3
Ͳ
Ph
Avg
AI
41
AI
41
Flt_XXX[32]
F10:32
nvoNgWat3PAv_XXX
SNVT_count_inc_f
Negative
VARs
3
Ͳ
Ph
Avg
AI
42
AI
42
Flt_XXX[33]
F10:33
nvoNgVAR3PAv_XXX
SNVT_count_inc_f
VAs
3
Ͳ
Ph
Avg
AI
43
AI
43
Flt_XXX[34]
F10:34
nvoVA_3PhAvg_XXX
SNVT_count_inc_f
Positive
PF
3
Ͳ
Ph
Avg
AI
44
AI
44
Flt_XXX[35]
F10:35
nvoPsPF3PhAv_XXX
SNVT_count_inc_f
Negative
PF
3
Ͳ
PF
Avg
AI
45
AI
45
Flt_XXX[36]
F10:36
nvoNgPF3PhAv_XXX
SNVT_count_inc_f
VA
Ͳ
hours
Total
AI
46
AI
46
S32_XXX[8]
F11:8
nvoVAh_Tot_XXX
SNVT_count_inc_f
Meter
Status
AI
47
AI
47
Byt_XXX[0]
N14:0
nvoMtr_Stat_XXX
SNVT_count
Current
Date
&
Time
Reg
1
AI
48
AI
48
Dev1_XXX[0]
N12:0
nvoCurDatTm1_XXX
SNVT_count
Current
Date
&
Time
Reg
2
AI
49
AI
49
Dev1_XXX[1]
N12:1
nvoCurDatTm2_XXX
SNVT_count
Current
Date
&
Time
Reg
3
AI
50
AI
50
Dev1_XXX[2]
N12:2
nvoCurDatTm3_XXX
SNVT_count
Positive
Watts
3
Ͳ
Ph
Max
Avg
Demand
AI
51
AI
51
Flt_XXX[37]
F10:37
nvoPWt3PMADm_XXX
SNVT_count_inc_f
Positive
VARs
3
Ͳ
Ph
Max
Avg
Demand
AI
52
AI
52
Flt_XXX[38]
F10:38
nvoPVr3PMADm_XXX
SNVT_count_inc_f
Negative
Watts
3
Ͳ
Ph
Max
Avg
Demand
AI
53
AI
53
Flt_XXX[39]
F10:39
nvoNWt3PMADm_XXX
SNVT_count_inc_f
Negative
VARs
3
Ͳ
Ph
Max
Avg
Demand
AI
54
AI
54
Flt_XXX[40]
F10:40
nvoNVr3PMADm_XXX
SNVT_count_inc_f
CT
multiplier
AI
55
AI
55
Byt_XXX[1]
N14:1
nvoCT_mult_XXX
SNVT_count
CT
denominator
AI
56
AI
56
Byt_XXX[2]
N14:2
nvoCT_den_XXX
SNVT_count
CT
numerator
AI
57
AI
57
Dev2_XXX[0]
N13:0
nvoCT_num_XXX
SNVT_count
PT
numerator
AI
58
AI
58
Dev2_XXX[1]
N13:1
nvoPT_num_XXX
SNVT_count
PT
denominator
AI
59
AI
59
Dev2_XXX[2]
N13:2
nvoPT_den_XXX
SNVT_count
PT
hookup
AI
60
AI
60
Byt_XXX[3]
N14:3
nvoPT_hookup_XXX
SNVT_count
PT
multiplier
AI
61
AI
61
Byt_XXX[4]
N14:4
nvoPT_mult_XXX
SNVT_count
Serial
Number
Reg
1
AI
62
AI
62
Dev2_XXX[4]
N13:4
nvoSerNum1_XXX
SNVT_count
Serial
Number
Reg
2
AI
63
AI
63
Dev2_XXX[5]
N13:5
nvoSerNum2_XXX
SNVT_count
Serial
Number
Reg
3
AI
64
AI
64
Dev2_XXX[6]
N13:6
nvoSerNum3_XXX
SNVT_count
Serial
Number
Reg
4
AI
65
AI
65
Dev2_XXX[7]
N13:7
nvoSerNum4_XXX
SNVT_count
Serial
Number
Reg
5
AI
66
AI
66
Dev2_XXX[8]
N13:8
nvoSerNum5_XXX
SNVT_count
Serial
Number
Reg
6
AI
67
AI
67
Dev2_XXX[9]
N13:9
nvoSerNum6_XXX
SNVT_count