2: Using the ProtoCom/ProtoCom-Lon
2.5: Step 5: Set the Baud Rate for BACnet MS/TP and DF1 Protocols
Use DIP Switches B0 - B3 to set the serial baud rate to match the baud rate provided
by the BMS for BACnet MS/TP and DF1.
Figure 2.3: B Bank of DIP Switches
NOTES:
• The baud rate for Metasys N2 protocol
is set to 9600: the B bank of DIP
Switches is disabled for Metasys N2 on
ProtoCom, since they are not needed.
• The B bank of DIP switches is disabled
for the ProtoCom-Lon.
• The default setting of the ProtoCom is
38400.
The following table shows the Baud Rate DIP Switch selection.
Baud
B0
B1
B2
B3
9600
On
On
On
Off
19200
Off
Off
Off
On
38400
On
On
Off
On
57600
Off
Off
On
On
76800
On
Off
On
On
B0 B1 B2 B3