12.9.4
High pressure protection (excluding RH Group)
Mode: (Auto) Heating
Fan:
Any
Timer:
Any
I Feel: On or Off
Control
Function
Protect the Compressor from high pressure by switching OFF the OFAN and COMP.
ICT [
o
c]
Any
Off
Any
Off
COMP
OFAN
52
55
61
66
COMP is forced OFF
67
OFAN is force
Off
COMP is forced OFF
For all models except WAX
For WAX model
ON
BLINK
OPER
LED
Notes:
•
IFAN, HE1 and HE2 will be activated according to the relevant
Heating Mode Sect.
•
In case of any malfunction in the relay control circuit, the OCT is also
monitored during heating mode. Whenever OCT reaches 70
o
c, which indicates
a high pressure in the outdoor coil, the COMP will be forced off automatically.
The COMP can be turned on again only after the 3 min COMP ON delay and the
OCT is under 70
o
c. The OPER LED will not blink in this case.
Summary of Contents for Gcz 12
Page 19: ...4 2 OUTLINE DIMENSIONS Revision Y05 01 Service Manual WMZ 4 3 GCZ 7 9 12 4 4 GCZ 17...
Page 20: ...4 3 OUTLINE DIMENSIONS Revision Y05 01 Service Manual WMZ 4 5 GCZ 22...
Page 147: ...15 2 OPTIONAL ACCESSORIES Revision Y05 01 Service Manual WMZ...
Page 148: ...15 3 OPTIONAL ACCESSORIES Revision Y05 01 Service Manual WMZ...
Page 149: ...15 4 OPTIONAL ACCESSORIES Revision Y05 01 Service Manual WMZ...
Page 150: ...15 5 OPTIONAL ACCESSORIES Revision Y05 01 Service Manual WMZ...
Page 178: ......
Page 179: ......
Page 180: ......
Page 181: ......
Page 182: ......
Page 183: ......
Page 184: ......
Page 185: ......
Page 186: ......
Page 187: ......
Page 188: ......
Page 189: ......
Page 190: ......
Page 191: ......
Page 192: ......
Page 193: ......
Page 194: ......
Page 195: ......
Page 196: ......
Page 197: ......
Page 198: ......
Page 199: ......
Page 200: ......
Page 201: ......
Page 202: ......
Page 203: ......
Page 204: ......
Page 205: ......