12-7
CONTROL SYSTEM
Revision Y05-01
Service Manual - WMZ
12.5
Cooling Mode - General
1)
Room Temperature, RT, is detected by
•
RAT in normal operation, or
•
RCT (R/C sensor) in I-FEEL mode.
2)
The resolution of RT is 1
o
c.
•
RT is activating COMP/WVL if (RT > SPT), and
•
RT is stopping COMP/WVL if (RT =< SPT).
3)
Indoor Coil Temp is detected by ICT (RT2).
4)
Outdoor Coil Temp is detected by OCT (RT3).
5)
OFAN OPERATIONS
•
OFAN starts together with COMP in general.
12.5.1 Cooling
Mode: Cool, Auto (at Cooling)
Temp: Selected desired temperature.
Summary of Contents for Gcz 12
Page 19: ...4 2 OUTLINE DIMENSIONS Revision Y05 01 Service Manual WMZ 4 3 GCZ 7 9 12 4 4 GCZ 17...
Page 20: ...4 3 OUTLINE DIMENSIONS Revision Y05 01 Service Manual WMZ 4 5 GCZ 22...
Page 147: ...15 2 OPTIONAL ACCESSORIES Revision Y05 01 Service Manual WMZ...
Page 148: ...15 3 OPTIONAL ACCESSORIES Revision Y05 01 Service Manual WMZ...
Page 149: ...15 4 OPTIONAL ACCESSORIES Revision Y05 01 Service Manual WMZ...
Page 150: ...15 5 OPTIONAL ACCESSORIES Revision Y05 01 Service Manual WMZ...
Page 178: ......
Page 179: ......
Page 180: ......
Page 181: ......
Page 182: ......
Page 183: ......
Page 184: ......
Page 185: ......
Page 186: ......
Page 187: ......
Page 188: ......
Page 189: ......
Page 190: ......
Page 191: ......
Page 192: ......
Page 193: ......
Page 194: ......
Page 195: ......
Page 196: ......
Page 197: ......
Page 198: ......
Page 199: ......
Page 200: ......
Page 201: ......
Page 202: ......
Page 203: ......
Page 204: ......
Page 205: ......