12-11
CONTROL SYSTEM
Revision Y05-01
Service Manual - WMZ
12.6.3 HE
operation
•
For
all Groups
, HE can be ON only when IFAN is ON.
•
For
all Groups
, HE switches to OFF when ICT > 50
o
c, and is activated
again when ICT
≤
45
o
c.
•
In
SH or RC group
, HE operation is limited by the following graph:
•
Back-up mode for
SH group
After COMP has been working for 5 minutes, HE & IFAN are activated even
if the ICT is still below 35
o
c. This situation is called Back-up Mode. Both
HE & IFAN will work in Back-up Mode until the ICT reaches 35
o
c. Then, the
operation goes on in the usual mode .
HE
ON
OFF
30
45
50
ICT [
o
c]
15
General :
For WAX :
35
20
40
Summary of Contents for Gcz 12
Page 19: ...4 2 OUTLINE DIMENSIONS Revision Y05 01 Service Manual WMZ 4 3 GCZ 7 9 12 4 4 GCZ 17...
Page 20: ...4 3 OUTLINE DIMENSIONS Revision Y05 01 Service Manual WMZ 4 5 GCZ 22...
Page 147: ...15 2 OPTIONAL ACCESSORIES Revision Y05 01 Service Manual WMZ...
Page 148: ...15 3 OPTIONAL ACCESSORIES Revision Y05 01 Service Manual WMZ...
Page 149: ...15 4 OPTIONAL ACCESSORIES Revision Y05 01 Service Manual WMZ...
Page 150: ...15 5 OPTIONAL ACCESSORIES Revision Y05 01 Service Manual WMZ...
Page 178: ......
Page 179: ......
Page 180: ......
Page 181: ......
Page 182: ......
Page 183: ......
Page 184: ......
Page 185: ......
Page 186: ......
Page 187: ......
Page 188: ......
Page 189: ......
Page 190: ......
Page 191: ......
Page 192: ......
Page 193: ......
Page 194: ......
Page 195: ......
Page 196: ......
Page 197: ......
Page 198: ......
Page 199: ......
Page 200: ......
Page 201: ......
Page 202: ......
Page 203: ......
Page 204: ......
Page 205: ......