Troubleshooting
98
Electrical Control System
2.3 Outdoor unit malfunction
Display
LED STATUS
E0
Outdoor EEPROM malfunction
E2
Indoor / outdoor units communication error
E3
Communication malfunction between IPM board and outdoor main board
E4
Open or short circuit of outdoor unit temperature sensor(T3,T4,T5,T2B)
E5
Voltage protection
E8
Outdoor fan speed has been out of control
F1
No A Indoor unit coil outlet temperature sensor or connector of sensor is defective
F2
No B Indoor unit coil outlet temperature sensor or connector of sensor is defective
F3
No C Indoor unit coil outlet temperature sensor or connector of sensor is defective
F4
No D Indoor unit coil outlet temperature sensor or connector of sensor is defective
F5
No E Indoor unit coil outlet temperature sensor or connector of sensor is defective
P1
High pressure protection (For ELAU-VCZ430-H11,
ELAU-VCZ536-H11)
P2
Low pressure protection (For ELAU-VCZ430-H11,
ELAU-VCZ536-H11)
P3
Current protection of compressor
P4
Temperature protection of compressor discharge
P5
High temperature protection of condenser
P6
IPM module protection
Note: Once these error codes display, they will disappear in at least 30 seconds if the unit come back to
normal.(Except E3&E4)
Summary of Contents for ELAU-VCZ218-H11
Page 13: ...Indoor Units Indoor Units 11 Part 2 Indoor Units JKD Type 12 Light Commercial 22...
Page 20: ...Exploded View and Spare Part list 18 Indoor Units Exploded View of indoor unit ELSI JKD012 N11...
Page 22: ...Exploded View and Spare Part list 20 Indoor Units Exploded View of indoor unit ELSI JKD018 N11...
Page 36: ...Dimensions 34 Indoor Units...
Page 38: ...Service Space unit mm 36 Indoor Units 3 3 Console...
Page 40: ...Wiring Diagrams 38 Indoor Units ELSI OCD012 N11 ELSI QAD012 N11...
Page 41: ...Wiring Diagrams Light Commercial 39...
Page 44: ...Exploded View and Spare Part list 42 Indoor Units Exploded View of indoor unit ELSI OCD012 N11...
Page 46: ...Exploded View and Spare Part list 44 Indoor Units Exploded View of indoor unit ELSI QAD012 N11...
Page 52: ...Dimensions 50 Outdoor Units ELAU VCZ536 H11...
Page 56: ...Wiring Diagrams 54 Outdoor Units 4 Wiring Diagrams ELAU VCZ218 H11 ELAU VCZ327 H11...
Page 57: ...Wiring Diagr ams Outdoor Units 55 ELAU VCZ430 H11 ELAU VCZ536 H11...
Page 125: ...SERVICE MANUAL Multi Splits Series...