Troubleshooting
Electrical Control System
117
2.4.2.10 IPM module protection(ODU P6)
IPM module protection
Check whether the voltage range
of P-N on IPM module is normal?
DC277-356V for 18-27KBtu/h;
DC277-410V for 36KBtu/h
Yes
Yes
No
Yes
Check whether the input
power supply is correct?
208-230V, 1N, 60Hz
No
No
Regulate it to correct, then
check whether the system
can work normally?
Check whether the
power supply line is
connected correctly and
tightly
Yes
Connect it correctly
and tightly, check ok
or not?
No
Check whether the connecting
line between main board and
the IPM module is connected
tightly
Yes
Connect it tightly,
check ok or not?
No
No
No
Connect it well, check
ok or not?
Check whether the connecting
line of the compressor is
connected correctly or tightly
Replace the IPM module,
check whether the system can
work normally?
No
No
Replace the main board; check
whether the system can work
normally?
No
Replace the compressor, check
whether the system can work
normally?
Check whether the lines
in E-part box are
connected tightly
Yes
Connect it tightly,
check ok or not?
No
No
Yes
No
Replace the bridge rectifiers
Check whether the bridge rectifiers are
normal? Use the multimeter to measure
the resistance between each two
terminals, check whether there is the
condition that value of resistance is 0
Check whether the connecting line of
every reactor is normal? If the line is
broken, the resistance of the two ports is
∞
(
models except for M4OA-36HFN1-
Q
,
M4OD-28HFN1-Q
,
M5OC-36HFN1-
Q
);
Check whether the PFC module
broken (for M4OA-36HFN1-Q
,
M4OD-
28HFN1-Q
,
M5OC-36HFN1-Q)
Replace the connecting line or
reactor or replace the PFC
module(for M4OC-36HRFN1-M)
Yes
No
No
Yes
Trouble is solved
Check if the outdoor fan
runs properly or the outdoor
unit ventilation is good.
No
Check whether the resistance of
the fan motor is normal. If not,
replace the fan motor.
For other
models, r
efer to the solution of
fan speed has been out of
control malfunction . F i n d o u t
the cause and have it solved.
Yes
Yes
Yes
Summary of Contents for ELAU-VCZ218-H11
Page 13: ...Indoor Units Indoor Units 11 Part 2 Indoor Units JKD Type 12 Light Commercial 22...
Page 20: ...Exploded View and Spare Part list 18 Indoor Units Exploded View of indoor unit ELSI JKD012 N11...
Page 22: ...Exploded View and Spare Part list 20 Indoor Units Exploded View of indoor unit ELSI JKD018 N11...
Page 36: ...Dimensions 34 Indoor Units...
Page 38: ...Service Space unit mm 36 Indoor Units 3 3 Console...
Page 40: ...Wiring Diagrams 38 Indoor Units ELSI OCD012 N11 ELSI QAD012 N11...
Page 41: ...Wiring Diagrams Light Commercial 39...
Page 44: ...Exploded View and Spare Part list 42 Indoor Units Exploded View of indoor unit ELSI OCD012 N11...
Page 46: ...Exploded View and Spare Part list 44 Indoor Units Exploded View of indoor unit ELSI QAD012 N11...
Page 52: ...Dimensions 50 Outdoor Units ELAU VCZ536 H11...
Page 56: ...Wiring Diagrams 54 Outdoor Units 4 Wiring Diagrams ELAU VCZ218 H11 ELAU VCZ327 H11...
Page 57: ...Wiring Diagr ams Outdoor Units 55 ELAU VCZ430 H11 ELAU VCZ536 H11...
Page 125: ...SERVICE MANUAL Multi Splits Series...