Troubleshooting
Electrical Control System
115
2.4.2.8 Temperature protection of compressor discharge(ODU P4)
Temperature protection of
compressor discharge
Check whether the
compressor discharge temp.
is more than 115°C ?
Check whether the wiring
connection is right between
compressor discharge temp.
sensor and PCB according
to wiring diagrams?
Method: Check whether the
resistance of compressor
discharge temp. sensor is
right refer to the
Appendix
2
No
Yes
Yes
Trouble is solved
No
Judge: The
discharge temp.
sensor is broken
Check whether the
refrigerant is leak
Correct the wiring connection
Stop leaking and add refrigerant
Replace the compressor discharge temp. sensor
No
Yes
Replace outdoor main board
Yes
Summary of Contents for ELAU-VCZ218-H11
Page 13: ...Indoor Units Indoor Units 11 Part 2 Indoor Units JKD Type 12 Light Commercial 22...
Page 20: ...Exploded View and Spare Part list 18 Indoor Units Exploded View of indoor unit ELSI JKD012 N11...
Page 22: ...Exploded View and Spare Part list 20 Indoor Units Exploded View of indoor unit ELSI JKD018 N11...
Page 36: ...Dimensions 34 Indoor Units...
Page 38: ...Service Space unit mm 36 Indoor Units 3 3 Console...
Page 40: ...Wiring Diagrams 38 Indoor Units ELSI OCD012 N11 ELSI QAD012 N11...
Page 41: ...Wiring Diagrams Light Commercial 39...
Page 44: ...Exploded View and Spare Part list 42 Indoor Units Exploded View of indoor unit ELSI OCD012 N11...
Page 46: ...Exploded View and Spare Part list 44 Indoor Units Exploded View of indoor unit ELSI QAD012 N11...
Page 52: ...Dimensions 50 Outdoor Units ELAU VCZ536 H11...
Page 56: ...Wiring Diagrams 54 Outdoor Units 4 Wiring Diagrams ELAU VCZ218 H11 ELAU VCZ327 H11...
Page 57: ...Wiring Diagr ams Outdoor Units 55 ELAU VCZ430 H11 ELAU VCZ536 H11...
Page 125: ...SERVICE MANUAL Multi Splits Series...