Electrical Control Function
Electrical Control System
81
COOL_F6
ICOOLLMT2
COOL_F5
ICOOLLMT1
If the current frequency is lower than COOL_F4, the frequency will not be limited.
After 10s of the compressor start, if the current>ICOOL, the AC will display the failure for 30 seconds and stop. The AC
will restart 3 minutes later.
Heating mode:
Current frequency
(
Hz
)
Current limit value
(
A
)
Frequency limit
HEAT_F16
IHEATLMT12
Decrease the frequency to HEAT_F4 and run at HEAT_F4 for
3 minutes.
After that, the frequency will be adjusted according to the
capacity demand and rise to the upper level every 3 minutes
(When the frequency>Heat_F4 via capacity demand).
HEAT_F15
IHEATLMT11
HEAT_F14
IHEATLMT10
HEAT_F13
IHEATLMT9
HEAT_F12
IHEATLMT8
HEAT_F11
IHEATLMT7
HEAT_F10
IHEATLMT6
HEAT_F9
IHEATLMT5
HEAT_F8
IHEATLMT4
HEAT_F7
IHEATLMT3
HEAT_F6
IHEATLMT2
HEAT_F5
IHEATLMT1
If the current frequency is lower than HEAT_F4, the frequency will not be limited.
After 10s of the compressor start, if the current>IHEAT, the AC will display the failure for 30 seconds and stop. The AC
will restart 3 minutes later.
1.2.9 Indoor / outdoor units communication protection
If the indoor units cannot receive the feedback signal from the outdoor units for 2 minutes, the AC will stop
and display the failure.
1.2.10 Oil return
Running rules:
1. If the compressor frequency keeps lower than RET_OIL_FREQ1_ADD for RET_OIL_TIME1_ADD, the
AC will rise the frequency to RET_OIL_FREQ2_ADD for RET_OIL_TIME2_ADD and then resume to
former frequency.
2. The EXV will keep 300p while the indoor units will keep the current running mode.
3. If the outdoor ambient is higher than TempT4HeatLimit_ADD during the oil return, the AC quit oil return.
1.3 Operation Modes and Functions
1.3.1 Fan mode
(1) Outdoor fan and compressor stop.
(2) Temperature setting function is disabled, and no setting temperature is displayed.
(3) Indoor fan can be set to high/med/low/auto;
(4) The louver operates same as in cooling mode.
(5) Auto fan:
For Cassette
、
Duct
Summary of Contents for ELAU-VCZ218-H11
Page 13: ...Indoor Units Indoor Units 11 Part 2 Indoor Units JKD Type 12 Light Commercial 22...
Page 20: ...Exploded View and Spare Part list 18 Indoor Units Exploded View of indoor unit ELSI JKD012 N11...
Page 22: ...Exploded View and Spare Part list 20 Indoor Units Exploded View of indoor unit ELSI JKD018 N11...
Page 36: ...Dimensions 34 Indoor Units...
Page 38: ...Service Space unit mm 36 Indoor Units 3 3 Console...
Page 40: ...Wiring Diagrams 38 Indoor Units ELSI OCD012 N11 ELSI QAD012 N11...
Page 41: ...Wiring Diagrams Light Commercial 39...
Page 44: ...Exploded View and Spare Part list 42 Indoor Units Exploded View of indoor unit ELSI OCD012 N11...
Page 46: ...Exploded View and Spare Part list 44 Indoor Units Exploded View of indoor unit ELSI QAD012 N11...
Page 52: ...Dimensions 50 Outdoor Units ELAU VCZ536 H11...
Page 56: ...Wiring Diagrams 54 Outdoor Units 4 Wiring Diagrams ELAU VCZ218 H11 ELAU VCZ327 H11...
Page 57: ...Wiring Diagr ams Outdoor Units 55 ELAU VCZ430 H11 ELAU VCZ536 H11...
Page 125: ...SERVICE MANUAL Multi Splits Series...