Electrical Control Function
84
Electrical Control System
The auto fan acts as below rules:
a
b
c
d
5.0
4.0
2.5
1.0
6.0
T1-Ts
e
H
(H-L)*0.75+L
(H-L)*0.5+L
(H-L)*0.25+L
L
1.3.2.4 Condenser temperature protection
When T3>65
℃
for 3 seconds, the compressor will stop while the indoor fan and outdoor fan will continue.
When T3<52
℃
, the protection will release and the compressor will restart after 3 minutes.
1.3.2.5
Evaporator low temperature protection
When T2B<0
℃
for 250 seconds, the indoor unit has no capacity demand and resume till T2B>10
℃
.
When T2<4
℃
, the indoor has no capacity demand and resume till T2>8
℃
.
1.3.3 Heating Mode
1.3.3.1 Compressor running rules
The compressor will run at corresponding frequency according to the gross amendatory capacity demand.
Frequency
0
HEAT_F1
HEAT _F2
……
HEAT_F15
HEAT _F16
Amendatory capacity demand.
0
1
2
……
15
16
1.3.3.2 Outdoor fan running rules:
Summary of Contents for ELAU-VCZ218-H11
Page 13: ...Indoor Units Indoor Units 11 Part 2 Indoor Units JKD Type 12 Light Commercial 22...
Page 20: ...Exploded View and Spare Part list 18 Indoor Units Exploded View of indoor unit ELSI JKD012 N11...
Page 22: ...Exploded View and Spare Part list 20 Indoor Units Exploded View of indoor unit ELSI JKD018 N11...
Page 36: ...Dimensions 34 Indoor Units...
Page 38: ...Service Space unit mm 36 Indoor Units 3 3 Console...
Page 40: ...Wiring Diagrams 38 Indoor Units ELSI OCD012 N11 ELSI QAD012 N11...
Page 41: ...Wiring Diagrams Light Commercial 39...
Page 44: ...Exploded View and Spare Part list 42 Indoor Units Exploded View of indoor unit ELSI OCD012 N11...
Page 46: ...Exploded View and Spare Part list 44 Indoor Units Exploded View of indoor unit ELSI QAD012 N11...
Page 52: ...Dimensions 50 Outdoor Units ELAU VCZ536 H11...
Page 56: ...Wiring Diagrams 54 Outdoor Units 4 Wiring Diagrams ELAU VCZ218 H11 ELAU VCZ327 H11...
Page 57: ...Wiring Diagr ams Outdoor Units 55 ELAU VCZ430 H11 ELAU VCZ536 H11...
Page 125: ...SERVICE MANUAL Multi Splits Series...