background image

 

INSTALLATION MANUAL

 

RP71L7V1
RP100L7V1

RP71L7W1
RP100L7W1
RP125L7W1

RYP71L7V1
RYP100L7V1

RYP71L7W1
RYP100L7W1
RYP125L7W1

 

Split System air conditioners

Summary of Contents for RP71L7V1

Page 1: ...INSTALLATION MANUAL RP71L7V1 RP100L7V1 RP71L7W1 RP100L7W1 RP125L7W1 RYP71L7V1 RYP100L7V1 RYP71L7W1 RYP100L7W1 RYP125L7W1 Split System air conditioners...

Page 2: ...C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 1 1 2 2 2 H1 L1 3 3 H1 H2 L3 L1 L2 4 4 H1 H2 L4 L1 L3 L2 5 5...

Page 3: ...7 7 8 8 NOTES...

Page 4: ...se med v ra instruktioner respektive utstyr er i overensstemmelse med f lgende standard er eller andre normgivende dokument er under forutssetning av at disse brukes i henhold til v re instrukser vast...

Page 5: ...eakage electric shocks or fire When a unit is installed in a small room it is necessary to take measures so that the leaked refrigerant amount does not exceed the limit even if it leaks As for the mea...

Page 6: ...d Places where the indoor and outdoor units piping and wiring lengths come within the allowable ranges Places where water leaking from the unit cannot cause damage to the location e g in case of a blo...

Page 7: ...following Elevate the foundation as high as possible Remove the rear suction grille to prevent snow from accumulating on the rear fins 7 If you install the unit on a building frame please install a w...

Page 8: ...tween the branch and the indoor units L2 L4 should have the same size as the indoor connections Branch see marking on figures 3 4 Suction side obstacle Obstacle is present Discharge side obstacle 1 In...

Page 9: ...equal When using existing refrigerant piping Pay attention to the following points when using existing refrigerant piping In the following situations the existing piping should not be re used and new...

Page 10: ...torque 19 6 24 5 N m Check for refrigerant leakage after tighten the cap Cautions for handling service port After the work tighten the valve cover in place Tightening torque 10 8 14 7 N m Precautions...

Page 11: ...installer Confirm that the valves are firmly closed before leak test or vacuuming Set up for vacuuming and leak test see figure 7 Procedure for leak test Leak test must satisfy EN378 2 Piping size Fl...

Page 12: ...90 kg 3 Refrigerant charge amount R R1 R2 0 0 0 9 0 9 kg Complete charging of the refrigerant after a leak etc When the entire refrigerant pipe length is within 30 meters charge the refrigerant in ac...

Page 13: ...ure the ground wire to the shut off valve attachment plate so that it does not slide 2 Secure the ground wire to the shut off valve attachment plate one more time along with the electric wiring and th...

Page 14: ...are open Be sure to close the frontside panel before operation as not doing so can cause electric shock The refrigerant pressure may not rise even if the shut off valve is opened after an air purge i...

Page 15: ...l check for voltage imbalance If the error code UF is displayed on the remote contol check the inter unit branch wiring connection Diagnosis On the remote control LCD If the machine stops due to some...

Page 16: ...PRC W1 MODEL Phase reverse circuit Q1M Q2M Thermo switch M1F M2F Q3E Earth leak detector R1T Thermistor air R2T Thermistor coil R3T Thermistor discharche R4C V1 MODEL Resistor RC Signal receiver circu...

Page 17: ...NOTES NOTES...

Page 18: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PWEN14486 1B...

Reviews: