Allowable pipe length and height difference

See the table below concerning lengths and heights. Refer to figures
2~4. Assume that the longest line in the figure corresponds with the
actual longest pipe, and the highest unit in the figure corresponds
with the actual highest unit.

The minimal piping length should be 5 m. If installation is performed
with less field piping, the system will be overcharged (abnormal HP,
etc.). If the distance between indoor and outdoor unit is less than
5 m, please make sure that the piping length is 

5 m by additional

bending of the pipes.

P

RECAUTIONS

 

ON

 

REFRIGERANT

 

PIPING

Do not allow anything other than the designated refrigerant to
get mixed into the freezing cycle, such as air, etc. If any
refrigerant gas leaks while working on the unit, ventilate the
room thoroughly right away.

Use R-407C only when adding refrigerant
Installation tools:
Make sure to use installation tools (gauge manifold charge hose,
etc.) that are exclusively used for R-407C installations to
withstand the pressure and to prevent foreign materials (e.g.
mineral oils and moisture) from mixing into the system.
Vacuum pump:
Use a 2-stage vacuum pump with a non-return valve
Make sure the pump oil does not flow oppositely into the system
while the pump is not working.
Use a vacuum pump which can evacuate to –100.7 kPa (5 Torr,
–755 mmHg).

In order to prevent dirt, liquid or dust from entering the piping,
cure the piping with a pinch or taping.

Great caution is needed when passing copper tubes through
walls.

In case of simultanious operating system
-

Upward and downward piping should be performed at the 
main piping line.

-

Use branch piping kit (optional) for branching refrigerant 
pipes.

Precautions to be taken. (For details, refer to the manual attached to
branch piping kit.)

-

Install the branch pipes horizontally. (Maximum inclination: 
20° or less)

-

Length of branch pipe to the indoor unit should be as short as 
possible.

-

Try to keep lengths of both branch pipes to the indoor unit 
equal.

When using existing refrigerant piping
Pay attention to the following points when using existing
refrigerant piping

In the following situations, the existing piping should not be
re-used and new piping should be installed.
- If the previously used model had problems with its 

compressor (this might cause oxidized coolant oil, scale 
residue and other adverse effects).

- If the indoor or outdoor units were disconnected from the 

piping for a long period of time (water or dirt might have 
gotten into the piping).

- If copper piping is corroded.

Flares should not be re-used but rather new ones made in
order to prevent leaks.

Check welded connections for gas leaks, if the local piping
has welded connections.

Replace deteriorated insulation with new material.

R

EFRIGERANT

 P

IPING

Field pipes can be installed in four directions.

Figure - Field pipes in four directions

Cutting out the two slits makes it possible to install as shown in
the 

figure "Field pipes in four directions"

.

(Use a metal saw to cut out the slits.)

To  install the connecting pipe to the unit in a downward
direction, make a knockout hole by penetrating the center area
around the knockout hole using a 

Ø

6 mm drill. (See 

figure "Field

pipes in four directions"

.)

After knocking out the knock-out, it is recommended to apply
repair paint to the edge and the surrounding end surfaces to
prevent rusting.

Allowable pipe length

Maximum allowable piping 
length (Parenthesized figure 
represents equivalent length)

Pair

L1

70 m 

(90 m)

Twin/Triple

L1+L2

Maximum total one-way pipe 
length

Twin

L1+L2+L3

80 m

Triple

L1+L2+L3+L4

Maximum branch pipe length

Twin/Triple

L2

20 m

Maximum difference between 
branch lengths

Twin

L2-L3

10 m

Triple

L2-L4

Maximum height between 
indoor and outdoor

All

H1

30 m

Maximum height between 
indoors

Twin/Triple

H2

0.5 m

Chargeless length

All

L1+L2+L3+L4

30 m

Place

Installation period

Protection method

Outdoor unit

More than a month

Pinch the pipe

Less than a month

Pinch or tape the pipe

Indoor

Regardless of the 

period

1

Drill

2

Center area around knockout hole

3

Knockout hole

4

Slit

5

Connecting pipe

6

Bottom frame

7

Front plate

8

Pipe outlet plate

9

Screw front plate

10

Pipe outlet plate screw

A

Forward

B

Backward

C

Sideways

D

Downward

4

4

3

2

1

7

8

9

10

A

D

C

B

5

6

Summary of Contents for RP71L7V1

Page 1: ...INSTALLATION MANUAL RP71L7V1 RP100L7V1 RP71L7W1 RP100L7W1 RP125L7W1 RYP71L7V1 RYP100L7V1 RYP71L7W1 RYP100L7W1 RYP125L7W1 Split System air conditioners...

Page 2: ...C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 1 1 2 2 2 H1 L1 3 3 H1 H2 L3 L1 L2 4 4 H1 H2 L4 L1 L3 L2 5 5...

Page 3: ...7 7 8 8 NOTES...

Page 4: ...se med v ra instruktioner respektive utstyr er i overensstemmelse med f lgende standard er eller andre normgivende dokument er under forutssetning av at disse brukes i henhold til v re instrukser vast...

Page 5: ...eakage electric shocks or fire When a unit is installed in a small room it is necessary to take measures so that the leaked refrigerant amount does not exceed the limit even if it leaks As for the mea...

Page 6: ...d Places where the indoor and outdoor units piping and wiring lengths come within the allowable ranges Places where water leaking from the unit cannot cause damage to the location e g in case of a blo...

Page 7: ...following Elevate the foundation as high as possible Remove the rear suction grille to prevent snow from accumulating on the rear fins 7 If you install the unit on a building frame please install a w...

Page 8: ...tween the branch and the indoor units L2 L4 should have the same size as the indoor connections Branch see marking on figures 3 4 Suction side obstacle Obstacle is present Discharge side obstacle 1 In...

Page 9: ...equal When using existing refrigerant piping Pay attention to the following points when using existing refrigerant piping In the following situations the existing piping should not be re used and new...

Page 10: ...torque 19 6 24 5 N m Check for refrigerant leakage after tighten the cap Cautions for handling service port After the work tighten the valve cover in place Tightening torque 10 8 14 7 N m Precautions...

Page 11: ...installer Confirm that the valves are firmly closed before leak test or vacuuming Set up for vacuuming and leak test see figure 7 Procedure for leak test Leak test must satisfy EN378 2 Piping size Fl...

Page 12: ...90 kg 3 Refrigerant charge amount R R1 R2 0 0 0 9 0 9 kg Complete charging of the refrigerant after a leak etc When the entire refrigerant pipe length is within 30 meters charge the refrigerant in ac...

Page 13: ...ure the ground wire to the shut off valve attachment plate so that it does not slide 2 Secure the ground wire to the shut off valve attachment plate one more time along with the electric wiring and th...

Page 14: ...are open Be sure to close the frontside panel before operation as not doing so can cause electric shock The refrigerant pressure may not rise even if the shut off valve is opened after an air purge i...

Page 15: ...l check for voltage imbalance If the error code UF is displayed on the remote contol check the inter unit branch wiring connection Diagnosis On the remote control LCD If the machine stops due to some...

Page 16: ...PRC W1 MODEL Phase reverse circuit Q1M Q2M Thermo switch M1F M2F Q3E Earth leak detector R1T Thermistor air R2T Thermistor coil R3T Thermistor discharche R4C V1 MODEL Resistor RC Signal receiver circu...

Page 17: ...NOTES NOTES...

Page 18: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PWEN14486 1B...

Reviews: