11-2
CONTROL SYSTEM
Revision Y05-02
Service Manual - WNG 50_60_80 DCI
11.3.2
Target Frequency Setting
The compressor target frequency is a function of the NLOAD number sent from
the indoor controller and the outdoor air temperature.
Basic Target Frequency Setting:
NLOAD
Target Frequency
127
Maximum frequency
10 < NLOAD < 127
Interpolated value between minimum and maximum frequency
10
Minimum frequency
0
Compressor is stopped
Target frequency limits as a function of outdoor air temperature (OAT):
OAT Range
Cool mode limits
Heat mode limits
OAT < 6
No limit
6 OAT < 15
MaxFreqAsOAT1H
15 OAT < 24
MaxFreqAsOATC
24 OAT
No limit
MaxFreqAsOAT2H
11.3.3
Frequency Changes Control
Frequency change rate is 1 Hz/sec.
11.3.4
Compressor Starting Control
Frequency
Time
Min 10 Minutes
1
Minute
Step 1
Step 3
1
Minute
Step 2
11.3.5
Minimum On and Off Time
3 minutes
Summary of Contents for DCI 80
Page 13: ...4 2 OUTLINE DIMENSIONS Revision Y05 02 Service Manual WNG 50_60_80 DCI 4 3 Outdoor Unit DCI 60...
Page 108: ......
Page 109: ......
Page 110: ......
Page 111: ......
Page 112: ......
Page 113: ......
Page 114: ......
Page 115: ......
Page 116: ......
Page 117: ......
Page 118: ......
Page 119: ......
Page 120: ......
Page 121: ......
Page 122: ......
Page 123: ......
Page 124: ......
Page 125: ......
Page 126: ......
Page 127: ......
Page 128: ......
Page 129: ......
Page 130: ......
Page 131: ......
Page 132: ......
Page 133: ......
Page 134: ......
Page 135: ......
Page 136: ......
Page 137: ......
Page 138: ......
Page 139: ......
Page 140: ......
Page 141: ......
Page 142: ......
Page 143: ......
Page 144: ......
Page 145: ......
Page 146: ......
Page 147: ......
Page 148: ......
Page 149: ......
Page 150: ......
Page 151: ......
Page 152: ......
Page 153: ......