12-18
CONTROL SYSTEM
Revision Y05-02
Service Manual - WNG 50_60_80 DCI
12.5.10.1 3 Levels Logic (used in floor/ceiling models)
P2
P3
Level
0
0
L0
1
0
L1
1
1
L2&3
0
1
L4
Water Level
ANY
0
BLINK
NLOAD
OPER LED
LEVEL1
LEVEL2&3
LEVEL4
NORMAL
ON
Pump
OFF
12.5.10.2 1 Level Logic (used in all models except for floor/ceiling models)
P2
P3
Level
Don’t care
1
Normal
Don’t care
0
Overflow
ANY
0
ON
NLOAD
PUMP
OFF
ON
OPER
LED
OFF
Overflow
Water Level
Normal
BLINK
NLOAD is
forced to 0
8 min
8 min
Overflow when
unit is ON
Overflow when
unit is OFF
8 min
Summary of Contents for DCI 80
Page 13: ...4 2 OUTLINE DIMENSIONS Revision Y05 02 Service Manual WNG 50_60_80 DCI 4 3 Outdoor Unit DCI 60...
Page 108: ......
Page 109: ......
Page 110: ......
Page 111: ......
Page 112: ......
Page 113: ......
Page 114: ......
Page 115: ......
Page 116: ......
Page 117: ......
Page 118: ......
Page 119: ......
Page 120: ......
Page 121: ......
Page 122: ......
Page 123: ......
Page 124: ......
Page 125: ......
Page 126: ......
Page 127: ......
Page 128: ......
Page 129: ......
Page 130: ......
Page 131: ......
Page 132: ......
Page 133: ......
Page 134: ......
Page 135: ......
Page 136: ......
Page 137: ......
Page 138: ......
Page 139: ......
Page 140: ......
Page 141: ......
Page 142: ......
Page 143: ......
Page 144: ......
Page 145: ......
Page 146: ......
Page 147: ......
Page 148: ......
Page 149: ......
Page 150: ......
Page 151: ......
Page 152: ......
Page 153: ......