14-2
TROUBLESHOOTING
Revision Y05-02
Service Manual - WNG 50_60_80 DCI
No
SYMPTOM
PROBABLE CAUSE
CORRECTIVE ACTION
7.
One indoor unit or more are
operating in cool mode with no
capacity, and the other units have
water leaks/freezing problems
The communication wires
of the indoor units are
switched
Check and correct the
communication wires
connection
8.
One indoor or more are operating in
heat mode with a limited capacity,
and the coil on the other units are
very hot.
9
Outdoor unit display board and leds
are off
No power supply
Check the connections and the
wiring on the main terminal -
Repair if needed.
PFC Chock coil
Check the PFC Chock coil
( 2.4.3)
Burnt fuse
Check 20A fuse on the Filter
( 2.4.2)
10.
Compressor operates but one or
more units generates no capacity
EEV problem
Check EEV ( 2.4.7)
Refrigerant leakage
Check refrigeration system
( 2.2)
Indoor coil block
Clean filters and/or remove
block
Outdoor coil block
Remove block and/or avoid air
by-pass
11.
Compressor is over heated and unit
does not generate capacity
EEV problem
Check EEV ( 2.4.7)
Refrigerant leakage
Check refrigeration system
( 2.2)
Indoor coil block
Clean filters and/or remove
block
Outdoor coil block
Remove block and/or avoid air
by-pass
12. Compressor stops during operation
Electronic control
Check diagnostics (see 2.3
below)
Refrigerant leakage
Check refrigeration system
( 2.2)
13. Not all units are operating
Communication problems
Check diagnostics (see 2.3
below)
14. Compressor does not start
Electronics control
problem or protection
15.
Unit works in wrong mode (cool
instead of heat or heat instead of
cool)
Electronics or RV problem
Check RV ( 2.4.6)
16.
All components are operating
properly but no cooling or no heating
Refrigerant leak
Check refrigeration system
( 2.2)
17.
Compressor motor is generating
noise and no suction occurs
Phase order to
compressor is wrong
Check compressor phase
order
18.
Freezing of outdoor unit in heat mode
and outdoor unit base is blocked with
ice
Connect base heater
19.
The unit stop suddenly during
operation
EMC interference to the
A/C unit
Check for EMC problems
( 2.4.10.1)
20.
Indoor unit(s) Indicator(s) leds may
flicker
21.
Other home appliances operation is
faulty such as noise appears in the
television picture, or the picture is
distorted or static occurs in the radio
sound
EMC interference by the
A/C unit
Check for EMC problems
( 2.4.10.2)
22
All others
Specific problems of
indoor or outdoor units
Check diagnostics (see 2.3
below)
Summary of Contents for DCI 80
Page 13: ...4 2 OUTLINE DIMENSIONS Revision Y05 02 Service Manual WNG 50_60_80 DCI 4 3 Outdoor Unit DCI 60...
Page 108: ......
Page 109: ......
Page 110: ......
Page 111: ......
Page 112: ......
Page 113: ......
Page 114: ......
Page 115: ......
Page 116: ......
Page 117: ......
Page 118: ......
Page 119: ......
Page 120: ......
Page 121: ......
Page 122: ......
Page 123: ......
Page 124: ......
Page 125: ......
Page 126: ......
Page 127: ......
Page 128: ......
Page 129: ......
Page 130: ......
Page 131: ......
Page 132: ......
Page 133: ......
Page 134: ......
Page 135: ......
Page 136: ......
Page 137: ......
Page 138: ......
Page 139: ......
Page 140: ......
Page 141: ......
Page 142: ......
Page 143: ......
Page 144: ......
Page 145: ......
Page 146: ......
Page 147: ......
Page 148: ......
Page 149: ......
Page 150: ......
Page 151: ......
Page 152: ......
Page 153: ......