7-1
ELECTRICAL DATA
Revision Y05-01
Service Manual - COMPACT
7.
ELECTRICAL DATA
7.1 Single
Phase
Units
MODEL COMPACT
7
COMPACT
9
COMPACT
12
To indoor
To indoor
To indoor
Power Supply
1PH-230V-50Hz 1PH-230V-50Hz 1PH-230V-50Hz
Max
Current,
A
5.4 6.7 8.5
Circuit Breaker
10
10
15
Power Supply Wiring No. X
Cross Section mm
2
3x1.0 mm
2
3x1.0
mm
2
3x1.5
mm
2
Interconnecting Cable RC
Model No. X Cross Section mm
2
5x1.0 mm
2
+2x0.5 mm
2
(OCT
senser)
5x1.0 mm
2
+2x0.5 mm
2
(OCT
senser)
5x1.5 mm
2
+2x0.5 mm
2
(OCT
senser)
Interconnecting Cable ST
Model No. X Cross Section mm
2
4x1.0 mm
2
4x1.0
mm
2
4x1.0
mm
2
NOTE
Power wiring cord should comply with local lows and electrical
regulations requirements.