5-13
PERFORMANCE DATA
Revision Y05-01
Service Manual - COMPACT
5.10 IOD7/CON7
R22
5.10.1
Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR
DB OD Coil(
o
C)
Data
ENTERING AIR WB/DB ID Coil(
o
C)
15/21
17/24
19/27
21/29
23/32
15
(1)
TC
2.23 2.31 2.37 2.42 2.46
SC
1.57 1.63 1.70 1.74 1.77
PI
0.53 0.53 0.53 0.53 0.54
20
(1)
TC
2.16 2.28 2.35 2.41 2.46
SC
1.54 1.62 1.69 1.74 1.77
PI
0.58 0.58 0.58 0.58 0.59
25
TC
2.05 2.21 2.32 2.39 2.45
SC
1.50 1.59 1.67 1.72 1.75
PI
0.62 0.63 0.63 0.64 0.64
30
TC
1.91 2.08 2.25 2.33 2.40
SC
1.45 1.54 1.64 1.69 1.72
PI
0.67 0.68 0.69
0.69 0.70
35
TC
1.77 1.92
2.12
2.23 2.33
SC
1.38 1.48
1.60
1.65 1.68
PI
0.73 0.74
0.75
0.76 0.76
40
TC
1.61 1.75 1.91
2.09 2.20
SC
1.30 1.40 1.51 1.56 1.59
PI
0.78 0.80 0.81 0.82 0.83
46
TC
1.40 1.53 1.68 1.86 2.00
SC
1.20 1.28 1.38 1.43 1.46
PI
0.86 0.87 0.89 0.90 0.91
LEGEND
TC –
Total Cooling Capacity, kW
SC – Sensible
Capacity,
kW
PI –
Power Input, kW
WB – Wet Bulb Temp., (
o
C)
DB –
Dry Bulb Temp., (
o
C)
ID
–
Indoor
OD –
Outdoor
(1) Marked area is below standard operating limits. For operating in low ambient
conditions, an A.S.K Kit is required.
Summary of Contents for CON 12
Page 104: ...15 2 OPTIONAL ACCESSORIES Revision Y05 01 Service Manual COMPACT...
Page 105: ...15 3 OPTIONAL ACCESSORIES Revision Y05 01 Service Manual COMPACT...
Page 106: ...15 4 OPTIONAL ACCESSORIES Revision Y05 01 Service Manual COMPACT...
Page 107: ...15 5 OPTIONAL ACCESSORIES Revision Y05 01 Service Manual COMPACT...
Page 110: ...AIR CONDITIONER SPLIT WALL MOUNTED PROGRAMMING AND OPERATING...
Page 128: ......
Page 129: ......