background image

ELCOS- Parma- Italy - GB  - CAM -684

10

Valid for firmware revisions higher than or equal to 1.24

STARTING CONSENT.  Operation obtained as during automatic mode.

Programming of telephone numbers of the users to inform when 

 alarm.

Refer to “Sending SMS messages” in the Modem Manual

the generator set is in

ADJUST THE CALENDAR CLOCK.            

The TIMER  permits to programme the operation or the block of the generating set.

WEEKLY AUTOMATIC TEST.  When WEEKLY AUTOMATIC TEST ENGAGED programming is finished, with

control unit in automatic mode, the generator set executes the test cycle.

               12:15

TO                     15:20

FROM

                 

333

333123456

              12:15

TO                    15:20

FROM

DAILY START

TIMER

WEEKLY AUTOMATIC

TEST

 Decreases

 Decreases

Increases

 Increases

Press and wait for

PROGRAMMED to be written

Press and wait for

PROGRAMMED to be written

Press and wait for

PROGRAMMED to be written

Press when the arrow is next

to the time to be corrected

Press to write number

Press to choose

USER PROGRAMMING

STOP

Press to

 

exit the

programming 

Press to select: 

PROGRAMMING

OPERATIONS

USER

PROGRAMMING

LANGUAGE CHOICE

WEEKLY AUTOMATIC

TEST

DAILY STOP

TIMER

DAILY START

TIMER

PRESS TO DISPLAY THE

REQUIRED PROGRAMMING

Decreases

LANGUAGE CHOICE.

 The language set up in the factory is ITALIAN the languages that can be selected are

SPANISH

: ENGLISH - FRENCH - 

                                                                                                                                                            GERMAN - 

 - PORTOGUESE.

LANGUAGE CHOICE

Press and wait for

PROGRAMMED to be written

Press to select

Press to display

EXCLU

ENGAGED

EXCLU

Factory setting

Press to display

STOP

STOP

Press to display

STOP

ACCESS TO PROGRAMMING MODE

(

led off

CALENDAR CLOCK ADJUSTMENT

ADJUSTMENT IS RECOMMENDED.

The time and date are used when the anomaly

log events are displayed.

CALENDAR CLOCK ADJUSTMENT

ADJUSTMENT

DAY MONTH YEAR

HOUR      MINUTES

Press for 2 seconds

until the number

      requiring editing

       flashes

If the power              is cut off, adjustment of the

calendar clock must be repeated. Installation of two

rechargeable batteries in the control unit shall prevent

a new setup.

WARNING: USE 

RECHARGEABLE BATTERIES ONLY. 

Non-rechargeable batteries may damage the control  

unit.

STOP

Moves

the cursor

Increases

TELEPHONE 1

TELEPHONE 3

TELEPHONE 2

STOP.  Stops starting or running of generator set.

                23:00

TO                      07:30

FROM

                23:00

TO                     07:30

FROM

DAILY STOP

TIMER

 Decreases

 Increases

Press and wait for

PROGRAMMED to be written

Press when the arrow is next

to the time to be corrected.

STOP

Press to display

ex

am

pl

e

ex

amp

le

ex

am

pl

e

No. user

No. mobile phone 

Press to move the cursor

cursor

 -   - 

2 3

Or

TELEPHONE 1

TELEPHONE 1

TELEPHONE 1

LANGUAGE CHOICE

ENGLISH

TEST

Cancels

C

Summary of Contents for CAM 684

Page 1: ...gram starting or stopping the generating set Generator start stop on request for power Possibility of starting the generating set in case of low battery charge Programmable weekly selftest Available inputs for fully programmable anomalies times polarities stopping possibility and message about the anomaly Three phase voltmetric control voltage failure undervoltage overvoltage asymmetryc voltage an...

Page 2: ...ply 1 2V Type AAA S U M M A R Y S u m m a ry T e c h n ic a l d a ta H is to ry o f re vis io n s P a g e 2 B rie f in s tru c tio n s In s tru m e n ts M o d e s o f c o m m u n ic a tio n o f th e c o n tro l u n it 3 O p e ra tio n F u n c tio n s s e le c tio n M a n u a l A u to m a tic T e s t O ff G lo w p lu g s p re h e a tin g S ta rtin g S ta rtin g F a ilu re 4 O p e ra tio n D e te c ...

Page 3: ... of 4000A or 110 of the full scale current of the chosen transformer From 0Hz to 85Hz for alternating voltages with amplitude KILOWATT HOUR Total PARTIAL HOUR METER With four digits and a maximum reading of 9999 hours and minutes The hours indicated are zeroset the next time the genset is started up TOTAL HOUR METER Displays five digits and a maximum reading of 59999 hours and minutes STARTING COU...

Page 4: ...e ime have elapsed the control unit commands the opening of the mains contactor and starts the generator set With engine running and generator voltage normal and once the GENERATOR TO POWER USERS CONNECTION DELAY has elapsed the generator contactor closes While it is running the generator set is protected from possible faults When the mains voltage is restored and the MAINS ACCEPTANCE time has ela...

Page 5: ... on the display STOPPING FAILED This intervenes if the running engine signal is detected 120 seconds after the stop command STOPPING FAILURE will be read on the display Do not use the emergency button combined with a stopping system that is not energized in run mode DETECTION OF RUNNING ENGINE It is obtained by detecting generator frequency and residual voltage or by detecting battery charger alte...

Page 6: ...XILIARY CONTACT GENERATOR CONTACTOR AUXILIARY CONTACT 22 21 13 in the Technical Programming Manual see page WIRING 36 32 75 76 L1 77 L2 78 L3 64 65 66 84 85 86 FOR THE CONNECTION OF A SINGLE AMMETER USE TERMINALS 75 77 GENERATOR MAINS AMMETERS DETECTION OF RUNNING ENGINE AND TACHOMETER DETECTION OF RUNNING ENGINE AND TACHOMETER DETECTION OF RUNNING ENG INE AND CHARGING ALTERNA TOR PRE EXCITATION W...

Page 7: ...ATE DIAGRAM GENER ATOR OVER LOAD SWITCH OIL PRESS URE TRANS MITTER TEMPER ATURE TRANS MITTER THERMO STATIC SWITCH OIL URE SWITCH PRESS GENERAL ALARM FU2 4A FU3 4A KM P FUEL LOADING SAFETY SOLENOID VALVE FUEL PUMP THER KM G SCREW ELECTRODES ROD ELECTRODE COOLANT LEVEL PROBE FOR RADIATORS WITH PLASTIC EXPANSION TANK FOR RADIATORS WITH METAL EXPANSION TANK 4 HAVING MADE THE CONNECTIONS THE CONTROL UN...

Page 8: ...njection control unit the engine will NOT cause to stop LED red FLASHING LIGHT anomaly managed by the control unit CAM 684 the engine will cause to stop LED yellow FLASHING LIGHT anomaly managed by the control unit CAM 684 the engine LEDS OFF ALL OK will NOT cause to stop INSTRUMENTS DESCRIPTION UNIT OF MEASURE MENT TACHOMETER Displays the number of engine revolutions rpm OIL PRESSURE GAUGE Displa...

Page 9: ...t is closed REMOTE STOP is shown on the display The control unit does not allow any startup operation and if the generator set is running it is stopped The intervention of the remote control is shown on the display EJP FUNCTION Choose EJP function see TECHNICAL PROGRAMMING manual on page 18 When the START UP contact connected to terminal 31 closes EJP STARTUP is seen on the display After the EJP S...

Page 10: ...reases LANGUAGE CHOICE The language set up in the factory is ITALIAN the languages that can be selected are SPANISH ENGLISH FRENCH GERMAN PORTOGUESE LANGUAGE CHOICE Press and wait for PROGRAMMED to be written Press to select Press to display EXCLU ENGAGED EXCLU Factory setting Press to display STOP STOP Press to display STOP ACCESS TO PROGRAMMING MODE led off CALENDAR CLOCK ADJUSTMENT ADJUSTMENT I...

Page 11: ... inside the control panel Never disconnect the terminals of the battery with running engine Never use a battery charger for the emergency start up the control unit could be damaged In order to safeguard people and equipment before connecting an external battery charger disconnect the electrical system terminals from the battery poles THIS CONTROL UNIT IS NOT SUITABLE FOR OPERATING IN THE FOLLOWING...

Page 12: ...A1 EN61000 4 2 EN61000 4 3 EN61000 4 4 EN61000 4 5 EN61000 4 6 EN60529 CONFORMITY DECLARATION BATTERY CHARGER We recommend fitting the plant with battery chargers compliant with DIN41773 standards BATTERY CHARGER OPERATION THREE CHARGING LEVELS RAPID WITH CURRENT CONTROL INTERMEDIATE MAINTENANCE WITH VOLTAGE CONTROL WHEN THE BATTERY CHARGER IS CONNECTED TO THE CAM 684 CONTROL UNIT THE DISPLAY SHOW...