Error Message List
Error Messages Displayed via
AGU Operating Panel
29
Display
flashes
code no.
Error description
Explanation of possible error causes, suggested corrections
10
Exterior temp. sensor – short or interrupted
Check AT sensor, emergency operation
20
VL boiler sensor
-
Short or interrupted
Check connection, notify service 2)
28
Exhaust sensor
-
Short or interrupted
Check connection, notify service 2)
40
RL boiler sensor
-
Short or interrupted
Check connection, notify service 2)
50
Reservoir sensor
-
Short or interrupted
Check connection, notify emergency service 2)
61
Fault room device QAA 73
Check QAA 73 room device and bus line
62
Wrong room device QAA 73
Connect proper QAA 73 room device
81
Short at LPB bus or no supply to bus
Check communication error, bus line, plug, etc.,
LPB bus feed not activated
82
Address collision at LPB bus
Check addressing of connected RVA...controller
91
Data
Internal LMU error, check process sensor, replace LMU,
notify service
92
Hardware error in electronics
Internal LMU error, check process sensor, replace LMU, notify ser-
vice
95
Invalid time
Correct time
100
Several time masters
System error, check clock master of RVA...controller
110
STB open, excessive temperature
No output of heat, standby function, cool off device and perform re-
set, if error occurs repeatedly, notify service 1)
113
Exhaust monitoring device triggered
Check connection, notify service 1)
130
Limit value exhaust temperature exceeded
Check connection, notify service 2)
132
Obstruction, input interrupted
Gas pressure monitor of external process tie
-
in open, for example 2)
133
LMU automated ignition locked, (no recog-
nition of flame after safety period)
Perform reset, if error occurs repeatedly, notify service,
check gas pressure, check polarity of power lines, ignition
system and ionization monitoring
134
Flame failure during operation
Perform reset 1)
135
Improper air supply
rpm threshold of blower exceeded or short of standard,
check parameters and for defective blower
140
Non
-
permitted LPB segment number or
device number
Configuration error, check setting of RVA.... controllers
148
Incompatible LPB interface / basic device
Configuration error, check setting of RVA.... controllers
151
Internal error LMU
Check LMU parameters, unlock LMU, replace LMU, notify service 2)
152
Error in LMU parameterization
Check LMU parameters, perform new LMU parameterization
153
TRIGON is locked,
Activate reset 1)
154
Plausibility criterion violated
Check LMU parameters
160
Rpm threshold not achieved
Blower defective of rpm threshold improperly set 1)
161
Maximum rpm exceeded
Max. blower rpm exceeded, check parameters
180
Chimney sweeper function active
Display only, no turn
-
off
181
Control valve stop function active
Display only, no turn
-
off
183
TRIGON is in programming mode
Display only, no turn
-
off
LED error display is permanently on if LMU error message cannot be changed.
In addition, the display of the diagnostics code flashes.
The error position is voided by pushing the reset button for more than 2 seconds.
1) Turn off and lock – unlock via rest only.
2) Turn off, prevent restart – restart after error correction only.