Commissioning
Boiler with internal system separation for secondary cycle
Pump / Setting / Resistance curves
17
Resistance curves plate heat exchanger (secondary cycle)
TRIGON L 65 / 85
TRIGON L 100 / 120
Boilers with integrated low loss header:
Boilers with integrated plate heat exchanger:
Boiler
TRIGON L 65
TRIGON L 85
TRIGON L 100
TRIGON L 120
Pump type speed controlled pump
UPM3 25
-
70
UPML 25
-
95 AUTO
Pump factory setting:
CC3
CP1
CP1
CP2
LED
dT at primary side (factory setting)
K
20
17
18
19
Max power consumption pump
W
40
80
80
110
Total max power consumption (pump)
W
180
274
302
355
Boiler
TRIGON L 65
TRIGON L 85
TRIGON L 100
TRIGON L 120
Pump type speed controlled pump
UPM3 25
-
70
UPML 25
-
95 AUTO
Pump factory setting:
CC3
CP1
CP1
CP2
LED
dT at primary side (factory setting)
K
18
16
17
18
Max power consumption pump
W
40
80
80
110
Total max power consumption (pump)
W
180
274
302
355