Parameterization for End User
Pos
AGU2.311
Parameter
Factory
Setting
Adjustment
Range
Units
Function
Time/Date
1
P1
0...23:59
hh:mm
Time
2
P2
1
-
7
Current day of the week (1=Monday)
Target Values
4
P5
16
20
-
85
Room temperature – reduced – target value
Timer Program HC1 (Heating Circuit 1)
P10
0
-
9
Day of the week timer setting HC1 (0; 1
-
7; 1
-
5; 6
-
7)
5
P11
06:00
00:00 ...24:00
hh:mm
Timer program HC1 Timer ON = Phase 1
6
P12
22:00
00:00 ...24:00
hh:mm
Timer program HC1 Timer OFF = Phase 1
7
P13
--
:
--
00:00 ...24:00
hh:mm
Timer program HC1 Timer ON = Phase 2
8
P14
--
:
--
00:00 ...24:00
hh:mm
Timer program HC1 Timer OFF = Phase 2
9
P15
--
:
--
00:00 ...24:00
hh:mm
Timer program HC1 Timer ON = Phase 3
10
P16
--
:
--
00:00 ...24:00
hh:mm
Timer program HC1 Timer OFF = Phase 3
Timer Program HC2 (Heating Circuit 2)
11
P20
0
-
9
Day of the week timer setting HC2 (0; 1
-
7; 1
-
5; 6
-
7)
12
P21
06:00
00:00 ...24:00
hh:mm
Timer program HC2 Timer ON = Phase 1
13
P22
22:00
00:00 ...24:00
hh:mm
Timer program HC2 Timer OFF = Phase 1
14
P23
--
:
--
00:00 ...24:00
hh:mm
Timer program HC2 Timer ON = Phase 2
15
P24
--
:
--
00:00 ...24:00
hh:mm
Timer program HC2 Timer OFF = Phase 2
16
P25
--
:
--
00:00 ...24:00
hh:mm
Timer program HC2 Timer ON = Phase 3
17
P26
--
:
--
00:00 ...24:00
hh:mm
Timer program HC2 Timer OFF = Phase 3
Timer Program DRW as Domestic Use Loading Program for Drinking Water
18
P30
0
-
9
Day of the week timer setting HC2 (0; 1
-
7; 1
-
5; 6
-
7)
19
P31
06:00
00:00 ...24:00
hh:mm
Timer program DRW Timer ON = Phase 1
20
P32
22:00
00:00 ...24:00
hh:mm
Timer program DRW Timer OFF = Phase 1
21
P33
--
:
--
00:00 ...24:00
hh:mm
Timer program DRW Timer ON = Phase 2
22
P34
--
:
--
00:00 ...24:00
hh:mm
Timer program DRW Timer OFF = Phase 2
23
P35
--
:
--
00:00 ...24:00
hh:mm
Timer program DRW Timer ON = Phase 3
24
P36
--
:
--
00:00 ...24:00
hh:mm
Timer program DRW Timer OFF = Phase 3
25
P45
no
no / yes
Standard timer program for HC1, HC2 and DRW
Parameter Setting
26
516
30
8
-
30
°C
Summer/Winter switch temperature
27
520
10
0
-
10
K
Drop amount for room target temperature with timers
28
532
15
1
-
40
Heating characteristic HC1
29
533
10
1
-
40
Heating characteristic HC2
30
534
0
-
31 <=> +31
K
Room target value correction HC1
31
535
0
-
31 <=> +31
K
Room target value correction HC2
32
629
0
End user may acknowledge a pending maintenance message
33
726
0
Contains a numeric maintenance code
34
727
50b
Internal diagnostics code
24
en