![elco RENDAMAX 30 Operating Instructions Manual Download Page 7](http://html1.mh-extra.com/html/elco/rendamax-30/rendamax-30_operating-instructions-manual_2377077007.webp)
Product description
Technical data
RENDAMAX 30
65 85 100 120
Nominal heat output at 75
o
/ 60
o
Max/Min
kW 58,8/8,3
77,5/15,5
87,2/17,4
108,9/21,8
Nominal heat output at 40
o
/ 30
o
C kW
65,1/9,2
85,8/17,2
96,5/19,3
120,5/24,1
Nominal heat load
kW 60,7/8,6
80,0/16,0
90,0/18,0
112,4/22,5
Standard efficiency 75
o
/ 60
o
C %
106,3
106,3
106,3
106,3
Standard efficiency 40
o
/ 30
o
C %
110,1
110,1
110,1
110,1
Operability losses T
K
= 70
o
C
%
< 0,3
< 0,3
< 0,3
< 0,3
Max. blower pressure
Pa
140
140
140
200
Water content
l
6,6
8,4
10,3
12,0
Max. permissible water pressure
bar
6
6
6
6
Max. permissible lead temperature
°C
90
90
90
90
Condensation volume at 40
o
C / 30
o
C
ca. l/h
9,7
12,8
14,4
18,0
Gas connection value
Natural gas
E/H*
(Hi=10.9
kWh/m
3
)
m
3
/h 5,6
7,3
8,2
10,3
Natural
gas
LL
(Hi=8.1
kWh/m
3
)
m
3
/h 7,5
9,9
11,1
13,9
Liquid
gas
propane
/
butane
(Hi=12.8 kWh/kg)
kg/h 4,7
6,3
7,1
8,8
Min. gas flow pressure
Natural gas
Liquid gas
mbar
mbar
20
50
20
50
20
50
20
50
Exhaust gas mass flow for natural gas
g/s
31
41
46
58
Exhaust gas temperature net, T
V
/T
R
75/60
°C
70
70
70
70
Exhaust gas temperature net, T
V
/T
R
40/30
°C
< 55
< 55
< 55
< 55
Gas category
II2ELL3P / II2H3P
Exhaust gas value group
G61
G61
G61
G61
Construction type - Exhaust gas systems
(B23; C13; C33; C43; C53; C63; C83)
All All All All
Ionisation flow min.
P$
15,0 15,0 15,0 15,0
Connections:
Air/exhaust gas pipe (concentric)
DN
80/125
110/150
110/150
110/150
Air/exhaust gas pipe (parallel)
DN
80/80
100/100
100/100
100/100
Heating lead / heating reflux (inner / outer)
DN
25/32
25/32
25/32
25/32
Gas
connection
DN 20
20
20
20
Condensation
pipe
connection
mm 25
25
25
25
pH value condensation
pH
3,0
3,0
3,0
3,0
Electric connection / power consumption 230 V / VAC
(*types 100 and 120 without boiler circuit pump)
W 230
255
130*
215*
CE ID number
0063BO3192
Weight, approx.
kg
55
65
80
90
Nominal heat output at 80
o
/60
o
C
kW
59,2
77,8
88,2
109,0
Efficiency at nominal output at 100%, 80
o
/60
o
C
%
97,5
97,3
98
97,7
Efficiency at partial load 30%, 40
o
/30
o
C
%
108,1
108,1
108,1
108,1
Operability losses at 70
o
C average K temp.
%
< 0,3
< 0,3
< 0,3
< 0,3
Auxiliary integrated boiler circuit pump
(*types 100 and 120 without boiler circuit pump)
W 147
171
83*
137*
7
Summary of Contents for RENDAMAX 30